'12 • PAC-T-174
Error code
Remote controller:
LED
Green
Red
Indoor
Outdoor
Content
-
365
-
None
Louver motor failure
(FDT, FDTC, FDEN, FDF series)
Keeps flashing
Stays OFF
Keeps flashing
Stays OFF
1. Applicable model
5. Troubleshooting
FDT, FDTC, FDEN, FDF series
only
Diagnosis
Countermeasure
NO
YES
Is LM wiring
broken?
Is LM locked?
�
Check at the indoor unit side.
LM: louver motor
Is the louver
operable with the remote
controller?
YES
NO
Does the louver
operate at the power
on?
YES
NO
YES
NO
Operate after
waiting for more
than 1 minute.
Repair wiring.
Defective indoor control
PCB
➞
Replace.
Replace LM.
Normal
Adjust LM lever and then
check again.
2. Error detection method
3. Condition of Error displayed
4. Presumable cause
• Defective LM
• LM wire breakage
• Faulty indoor control PCB
Note:
Summary of Contents for SRK100VNPZJX
Page 95: ... 94 12 PAC T 174 Models FDT100VF 125VF 140VF G H H H H A B F C D H G PJF000Z285 ...
Page 98: ... 97 12 PAC T 174 Models FDEN60VF 71VF C2 C1 A B F E G D B A C1 C2 C1 C2 PFA003Z817 B ...
Page 101: ... 100 12 PAC T 174 Models FDU200VF 250VF F F G B A C D E PJD001Z216 B ...
Page 113: ... 112 12 PAC T 174 b Wireless remote controller RCN E1R 60 17 150 Unit mm ...
Page 275: ... 274 12 PAC T 174 ...
Page 276: ... 275 12 PAC T 174 ...
Page 277: ... 276 12 PAC T 174 ...
Page 286: ... 285 12 PAC T 174 ...
Page 287: ... 286 12 PAC T 174 ...
Page 288: ... 287 12 PAC T 174 ...
Page 341: ... 340 12 PAC T 174 4GRNCEG VJG 2 Part number Power PCB Part number ...
Page 508: ... 507 12 PAC T 174 ...