499
-
'12 • PAC-T-174
Step 11
11. Reassemble the fan blade.
Take care to align the D-cut of motor shaft and the fan blade.
mark on the center of the fan shows the position of D-cut.
<Note>
1. Tightening torque of the nut is 4.0-4.9 N·m.
2. Do not rotate the axis of fan motor when tightening the nut.
It may cause malfunction of the fan motor.
Step 10
10. Insert the connector to the port (Model A:
CNN, Model B,C:CNF) on the PCB, and fix
the wire with bands. Excess part of the
wire should be dropped naturally.
<Note>
Be sure to cut the excess part of plastic band.
It may cause abnormal noise when hit by fan blade or misassembling of panels.
Do not bundle excess part of the wire. It may damage the heater.
<Note>
This heater should have bending radius of at least 25mm including non-heating part. Do not bundle the excess part of the wire. It may cause
disconnection of the heater or insufficient capacity.
Be sure to prevent the heater from touching any refrigerant piping.
Especially, pay close attention not to make it touch with pipes which are close to the wiring route such as suction pipe, check valve and check joint.
Model A
Model B
Model C
Connector CNN
(Yellow)
Band
Band
Connector CnF
(Black)
Connector CnF
(Black)
Connector CnF
(Black)
Summary of Contents for SRK100VNPZJX
Page 95: ... 94 12 PAC T 174 Models FDT100VF 125VF 140VF G H H H H A B F C D H G PJF000Z285 ...
Page 98: ... 97 12 PAC T 174 Models FDEN60VF 71VF C2 C1 A B F E G D B A C1 C2 C1 C2 PFA003Z817 B ...
Page 101: ... 100 12 PAC T 174 Models FDU200VF 250VF F F G B A C D E PJD001Z216 B ...
Page 113: ... 112 12 PAC T 174 b Wireless remote controller RCN E1R 60 17 150 Unit mm ...
Page 275: ... 274 12 PAC T 174 ...
Page 276: ... 275 12 PAC T 174 ...
Page 277: ... 276 12 PAC T 174 ...
Page 286: ... 285 12 PAC T 174 ...
Page 287: ... 286 12 PAC T 174 ...
Page 288: ... 287 12 PAC T 174 ...
Page 341: ... 340 12 PAC T 174 4GRNCEG VJG 2 Part number Power PCB Part number ...
Page 508: ... 507 12 PAC T 174 ...