background image

Designation: AIR CONDITIONER FOR ELECTRICAL ENCLOSURE

 

Page 1/16

 

UMA-CDZ-IP-ACOWM200-00

 

 

 

 

USER’S MANUAL (PART 2) 

 

 

AIR CONDITIONER FOR ELECTRICAL ENCLOSURE  

OUTDOOR APPLICATION 

 

 

 

IP-ACOWM200 

IP-ACOWM200.0X 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Document:

 UMA-CDZ-IP-ACOWM200-00

 

  

Date 

Name 

Description

 

 

Original user’s manual for air conditioner 

IP-ACOWM200

 series 

 

Language: English

 

 

ISSUE 

23/05/2021 

 

REV. 01 

 

 

REV. 02 

 

 

REV. 03 

 

 

Summary of Contents for IP-ACOWM200

Page 1: ...00 USER S MANUAL PART 2 AIR CONDITIONER FOR ELECTRICAL ENCLOSURE OUTDOOR APPLICATION IP ACOWM200 IP ACOWM200 0X Document UMA CDZ IP ACOWM200 00 Date Name Description Original user s manual for air con...

Page 2: ...closure there must not be components that could affect the proper ventilation Provide a proper fixing of the electrical enclosure to the floor to prevent accidental tipping due to the supplementary we...

Page 3: ...IP ACOWM200 0X FEATURES Unit Power supply V ph Hz 230 1 50 60 Cooling capacity EN14511 A35 A35 W 2000 2100 A35 A50 W 1200 1250 Absorbed electric power EN14511 A35 A35 W 1060 1100 A35 A50 W 1240 1300...

Page 4: ...y GENERAL CHECKS electrical enclosure must be disconnected form power supply electrical data shown on rating label pasted on air conditioner side must be guaranteed Electrical enclosure must be sized...

Page 5: ...IR CONDITIONER FOR ELECTRICAL ENCLOSURE Page 5 16 UMA CDZ IP ACOWM200 00 2 3 FITTING 1 Make the fixing hole on the enclosure as is shown in the drilling template Deburr all sharp edges to avoid accide...

Page 6: ...nscrewing included in mounting kit 5 Connect the condensate drain pipe like is shown in picture below Put some glue on aluminium pipe before to insert it Air conditioner produces condensate because th...

Page 7: ...ush the spring with a screwdriver and then insert the wire 2 Check the proper wire insertion 3 Connect the unit with the power supply Electrical data shown on rating label pasted on air conditioner si...

Page 8: ...Designation AIR CONDITIONER FOR ELECTRICAL ENCLOSURE Page 8 16 UMA CDZ IP ACOWM200 00 3 1 WIRING DIAGRAM 3 1 1 IP ACOWM200 IP ACOWM200 0X...

Page 9: ...nimum interval of two successive switch on of the compressor parameter C2 is elapsed Condenser fan turns ON when refrigerant pressure rises up to pressure switch set Compressor and condenser fan turn...

Page 10: ...ide 0 60 40 min U1 Select temperature display sensor 1 00 display cabinet sensor 01 display evaporator sensor 0 U2 Switch between Fahrenheit and Celsius 3 00 Fahrenheit 01 Celsius 01 U3 Select defrost...

Page 11: ...er selecting the menu press Set to enter the current menu and set its parameters Use or to adjust parameter values then press Set again to return to menu selection status 5 Under any parameter setting...

Page 12: ...if parameter U1 1 rH when temperature A6 and alarm delay time run out controller will display rH rL when temperature A5 and alarm delay time run out controller will display rL 5 SPARE PARTS LIST REFE...

Page 13: ...oling circuit has been modified about type and quantity of refrigerant or composition 2 the unit operates in acid or corrosive ambient 3 the unit has been modified without IP ENCLOSURES consent This w...

Page 14: ...E LOW VOLTAGE DIRECTIVE 26 February 2014 2014 30 UE EMC DIRECTIVE 26 February 2014 2011 65 UE ROHS DIRECTIVE 8 June 2011 STANDARDS APPLIED TO MEET THE PRINCIPAL ELEMENTS OF THE DIRECTIVE EN 60335 2 40...

Page 15: ...Designation AIR CONDITIONER FOR ELECTRICAL ENCLOSURE Page 15 16 UMA CDZ IP ACOWM200 00 SAA CERTIFICATE...

Page 16: ...Designation AIR CONDITIONER FOR ELECTRICAL ENCLOSURE Page 16 16 UMA CDZ IP ACOWM200 00 NOTES...