'12 • PAC-T-174
(5)
Defrosting
(a) Defrosting start conditions
If all of the following defrosting conditions A or conditions
B are met, the defrosting operation starts.
1)
Defrosting conditions A
a) Cumulative compressor operation time after the
end of defrosting has elapsed 37 minutes, and the
cumulative compressor operation time after the
start of heating operation (remote controller ON)
has elapsed 30 minutes.
b) After 5 minutes from the compressor ON
c) After 5 minutes from the start of outdoor unit fan
d) After satisfying all above conditions, if temperatures
of the outdoor unit heat exchanger temperature
thermistor (Tho-R1, R2) and the outdoor air
temperature thermistor (Tho-A) become lower
than the defrosting start temperature as shown
by the right figure for 15 seconds continuously,
or the suction gas saturation temperature (SST)
and the outdoor air temperature (Tho-A), which
are obtained from the value detected by the
low pressure sensor (LPT) stay for 3 minutes
within the range below the defrosting operation
start temperature as shown by the right figure.
However, it excludes for 10 minutes after the start
of compressor and the outdoor air temperature is
as shown by the lower figure.
LPT detection
Outdoor air temp. (°C)
2
4
LPT invalid
2)
Defrosting conditions B
a) When previous defrosting end condition is the time out of defrosting operation and it is in the heating operation
after the cumulative compressor operation time after the end of defrosting has become 30 minutes.
b) After 5 minutes from the start of compressor
c) After 5 minutes from the start of outdoor unit fan
(b) Defrosting end conditions
When any of the following conditions is satisfied, the defrosting end operation starts.
1)
When it has elapsed 8 minutes and 20 seconds after the start of defrosting. (After 10 minutes and 20 seconds for
model, 200 and 250)
2)
When the outdoor unit heat exchanger temperatures (Tho-R1, R2), whichever the lower, becomes 12°C or higher for
10 seconds continuously.
(c) Switching of defrosting control with SW3-1
1)
If SW3-1 on the outdoor unit control PCB is turned to ON, it becomes easier to enter the defrosting operation. Use
this when installing a unit at snowing regions.
2)
Control contents
a) It allows entering the defrosting operation under the defrosting condition A when the cumulative heating
operation time becomes 30 minutes. It is 37 minutes at SW3-1 OFF (Factory default).
b) It allows entering the defrosting operation under the defrosting condition B when the cumulative heating
operation time becomes 25 minutes. It is 30 minutes at SW3-1 OFF (Factory default).
c) It allows the defrosting operation with the outdoor unit heat exchanger temperature (Tho-R) and suction
pressure saturation temperature (SST) being higher than normal.
Outdoor air temp.
(
℃
)
[
Tho-A
]
Outdoor air temp.
(
℃
)
[
Tho-A
]
Suction
saturation
temp.
(
℃
)
[
SST
]
Suction
saturation
temp.
(
℃
)
[
SST
]
-20
-25
-28.6
-30
-24
-15
-10
-8
-15
-10
-5
0
5 6
10
-20
-25
Defrost
op
erat
ion
star
t tempe
rature
(S
tan
dar
d)
De
fro
st
oper
ation
start
tempe
rat
ure
(S
W
3-1
ON
)
-20
-25
-30
-31
-24
-15
-10
-8
-35
-15
-18
-10
-5
0
5 6
10
-25
-20
-18
Defrost
operation
start
temp
eratur
e (S
W3-1
ON)
D
efrost
ope
rat
ion
star
t t
emp
erature
(S
tandard)
Defrost operation start
temperature zone
Defrost operation start
temperature zone
Model 71
Model 100 ~ 250
Outdoor air temp. (
℃
)
[
Tho-A
]
-20
-25
-27
-30
-15
-10
-5
-6
-2
-15
-10
-5
0
5 6
10
-20
-25
Defrost operation start
temperature zone
Defrost
operation
start
temperature
(Standard)
Defrost
operation
start
tem
perat
ure
(SW3-1
ON)
Outdoor
unit
heat
exchanger
te
mp.
(
℃
)
[
Tho-R
]
-18
Model 71 ~ 250
Outdoor air temp.
(
℃
)
[
Tho-A
]
Outdoor air temp.
(
℃
)
[
Tho-A
]
Suction
saturation
temp.
(
℃
)
[
SST
]
Suction
saturation
temp.
(
℃
)
[
SST
]
-20
-25
-28.6
-30
-24
-15
-10
-8
-15
-10
-5
0
5 6
10
-20
-25
Defrost
op
erat
ion
star
t temperat
ure
(S
tan
dar
d)
De
fro
st
oper
ati
on
start
tempe
rat
ure
(S
W
3-1
ON
)
-20
-25
-30
-31
-24
-15
-10
-8
-35
-15
-18
-10
-5
0
5 6
10
-25
-20
-18
Defrost
operation
start
temp
eratur
e (S
W3-1
ON)
D
efrost
ope
rat
ion
star
t t
emp
erature
(S
tandard)
Defrost operation start
temperature zone
Defrost operation start
temperature zone
Model 71
Model 100 ~ 250
Outdoor air temp. (
℃
)
[
Tho-A
]
-20
-25
-27
-30
-15
-10
-5
-6
-2
-15
-10
-5
0
5 6
10
-20
-25
Defrost operation start
temperature zone
Defrost
operation
start
temperature
(Standard)
Defrost
operation
start
tem
perat
ure
(SW3-1
ON)
Outdoor
unit
heat
exchanger
te
mp.
(
℃
)
[
Tho-R
]
-18
Model 71 ~ 250
Summary of Contents for SRK100VNPZJX
Page 95: ... 94 12 PAC T 174 Models FDT100VF 125VF 140VF G H H H H A B F C D H G PJF000Z285 ...
Page 98: ... 97 12 PAC T 174 Models FDEN60VF 71VF C2 C1 A B F E G D B A C1 C2 C1 C2 PFA003Z817 B ...
Page 101: ... 100 12 PAC T 174 Models FDU200VF 250VF F F G B A C D E PJD001Z216 B ...
Page 113: ... 112 12 PAC T 174 b Wireless remote controller RCN E1R 60 17 150 Unit mm ...
Page 275: ... 274 12 PAC T 174 ...
Page 276: ... 275 12 PAC T 174 ...
Page 277: ... 276 12 PAC T 174 ...
Page 286: ... 285 12 PAC T 174 ...
Page 287: ... 286 12 PAC T 174 ...
Page 288: ... 287 12 PAC T 174 ...
Page 341: ... 340 12 PAC T 174 4GRNCEG VJG 2 Part number Power PCB Part number ...
Page 508: ... 507 12 PAC T 174 ...