345
-
'12 • PAC-T-174
after elapsing
3 minutes from
power OFF
connectors are not half inserted
2) Model FDC200,250VS
a) Replace the PCB
after elapsing 3 minutes from power OFF
.
(
Be sure to measure the voltage (DC) of two places
(1.Resistor on PCB at the front of controller
2.Both capacitor terminals located in back of controller), and
check that the voltage is discharged
sufficiently
. (Refer to Fig.1))
b) Disconnect the connectors from the control PCB.
c) Disconnect the blue wiring passing through CT1 on the substrate before replacing the PCB.
d) Match the setting switches (SW3-5,JSW) with the former PCB.
e) Tighten up a screw after passing blue wiring through CT1 of the changed.
f) Connect the connectors to the control PCB. (Confirm the
connectors are not half inserted
)
Parts No.
Parts Arrangement View
Fig.1 Position of capacitor
CNA2
CNIP
Voltage measurement parts
CNTH
CNPS
CNI1
CNA1
CNFAN1
CNEEV2
CNEEV1
CNS
CNR
CNH
CNW
CNW2
JSW
SW5
SW4
SW3
CNB
CNM
CNU
CNFAN2
CT1
Front View
Side View
Voltage measurement
parts
PCA012D017F
F
Summary of Contents for SRK100VNPZJX
Page 95: ... 94 12 PAC T 174 Models FDT100VF 125VF 140VF G H H H H A B F C D H G PJF000Z285 ...
Page 98: ... 97 12 PAC T 174 Models FDEN60VF 71VF C2 C1 A B F E G D B A C1 C2 C1 C2 PFA003Z817 B ...
Page 101: ... 100 12 PAC T 174 Models FDU200VF 250VF F F G B A C D E PJD001Z216 B ...
Page 113: ... 112 12 PAC T 174 b Wireless remote controller RCN E1R 60 17 150 Unit mm ...
Page 275: ... 274 12 PAC T 174 ...
Page 276: ... 275 12 PAC T 174 ...
Page 277: ... 276 12 PAC T 174 ...
Page 286: ... 285 12 PAC T 174 ...
Page 287: ... 286 12 PAC T 174 ...
Page 288: ... 287 12 PAC T 174 ...
Page 341: ... 340 12 PAC T 174 4GRNCEG VJG 2 Part number Power PCB Part number ...
Page 508: ... 507 12 PAC T 174 ...