background image

Model Numbers

ERQ2-16AS
ERQ3-18AS
ERQ5-21AS
ERQ5-24AS

IMPORTANT NOTE:

Please read this manual carefully before installing or operating your air conditioning unit.

That’s better. That’s Actron.

ESP Platinum QUE 
Split Ducted Unit - 3 Phase

Installation and Commisioning Guide - Indoor 

Summary of Contents for ERQ2-16AS

Page 1: ...Q5 21AS ERQ5 24AS IMPORTANT NOTE Please read this manual carefully before installing or operating your air conditioning unit That s better That s Actron ESP Platinum QUE Split Ducted Unit 3 Phase Installation and Commisioning Guide Indoor ...

Page 2: ...nimum Service Access Areas and Airflow Clearances 08 05 Installation Instructions 09 05 01 Lifting the Unit 09 05 02 Location 09 05 03 Condensate and Safety 09 05 04 Supply Air and Return Air Duct 09 05 05 Supply Air and Return Air Plenums Optional 09 05 06 Return Air Filter 10 05 07 Field Pipe Connection 10 05 08 Electrical Field Connection 10 06 Unit Lifting Procedures 11 06 01 Crane Lifting Met...

Page 3: ... instructions to ensure correct installation and safe operation of your air conditioning system IMPORTANT Keep this document for future reference Ensure all technicians that work on the unit can refer to this manual at any time 01 02 Product Inspections Check your air conditioning unit and all items against the invoice upon receiving your shipment Inspect the unit components and accessories for an...

Page 4: ... the appliance safely Young children should be supervised to ensure that they do not play with the appliance Installer must incorporate a means of electrical disconnection isolator in the sub mains fixed wiring in accordance with AS NZS 3000 2018 also known as Australian Wiring Rules Secure the power cords and control cables that goes in out the unit Use the cable ties provided in the control box ...

Page 5: ...ifications are subject to change without notice Copyright 2019 Actron Engineering Pty Ltd 03 Components Overview INDOOR UNIT COMPONENTS OVERVIEW INDOOR UNIT ID COIL ASSEMBLY ZONE MODULE COVER CONTROL PANEL EC ID Fan INDOOR CONTROL PANEL INDOOR PC BOARD FILTER BOARD SAFETY TRAY CONNECTION CONDENSATE DRAIN CONNECTION Applicable to ERQ5 21AS and ERQ5 24AS only ...

Page 6: ... 300 72 40 340 22 50 140 247 5 247 5 575 SUPPLY AIR RETURN AIR 1290 O A 40 535 70 50 EC INDOOR FAN SUPPLY AIR GAS PIPE Ø 19 05mm 3 4 SWAGED LIQUID PIPE Ø 9 52mm 3 8 SWAGED SAFETY DRAIN TRAY Ø 20mm ID CONDENSATE DRAIN Ø 20mm OD OVERALL NOMINAL DIMENSION H x W x D 412 x 1290 x 615 SUPPLY DUCT H x W 300 x 715 RETURN DUCT 340 x 1100 DRAIN CONNECTION 20mm OD TOP VIEW FRONT VIEW SIDE VIEW NOTE All dimen...

Page 7: ...x 695 SUPPLY DUCT H x W 380 x 715 RETURN DUCT 410 x 1190 DRAIN CONNECTION 25mm ID FRONT VIEW SIDE VIEW 1190 80 120 715 337 5 337 5 INDOOR COIL 1470 O A 695 O A 605 40 50 380 70 35 410 25 50 SUPPLY AIR RETURN AIR 645 20 20 1430 85 485 O A 130 SUPPLY AIR EC INDOOR FAN GAS PIPE Ø 25 4mm 1 SWAGED LIQUID PIPE Ø 12 7mm 1 2 SWAGED SAFETY DRAIN TRAY Ø 25mm ID CONDENSATE DRAIN Ø 25mm ID TOP VIEW NOTE All d...

Page 8: ...TRAY Ø 25mm ID CONDENSATE DRAIN Ø 25mm ID Model A B Height Clearance ERQ2 16AS ERQ3 18AS 800 800 340 ERQ5 21AS ERQ5 24AS 890 890 410 NOTES Do not scale drawing All dimensions are in mm unless specified Refer to corresponding unit dimensional drawing for mounting hole details Service Access Areas and Spaces for Airflow Clearances given above are suggested minimums based on the condition that the sp...

Page 9: ...nimum service access clearances provided in the unit drawings Locate the indoor unit away from the areas where noise is a critical factor Use rubber mounting pad not supplied in order to minimize the transfer of noise and vibration into building structures A hanging bracket assembly and rubber grommet optional on other units are also provided to secure the indoor unit into the roof rafters This co...

Page 10: ...ents vary Ensure that filters are cleaned replaced regularly 05 07 Field Pipe Connection Specifications and installation requirements for field pipe connections are contained in the Installation and Commissioning Guide of the outdoor unit that matches your indoor unit Please refer to this guide and thoroughly understand the procedures for safe and correct indoor and outdoor connection ActronAir hi...

Page 11: ...procedure and unit model shown are suggestions and for illustration purposes only It is highly recommended that installer observe current industry safe and sound rigging and lifting procedure SRD175C SR SELECTION DATA DIGITAL SCROLL COMPRESSOR SP SPLIT DUCTED UNIT Fig 1 Connect the loop ends of slings onto shackle DETAIL A Slip nylon slings through the pallet INDOOR UNIT PALLET SRD175C SRD175E LEC...

Page 12: ...PLY INDOOR 240V 1 P RATED LOAD AMPS OUTDOOR INDOOR TOTAL 22 0 3 FULL LOAD AMPS OUTDOOR INDOOR TOTAL 32 6 4 CIRCUIT BREAKER AND CABLE AMPS 40 APPROXIMATE STARTING AMPS 45 WEIGHT kg INDOOR OUTDOOR 75 0 OUTDOOR UNIT MODEL SRD1 INDOOR UNIT MODEL SRD1 Based on unit rating excluding indoor fan kW Measured and tested in accordance with AS NZS 3823 1 2 At 270 C DB 190 C WB entering air temperatures and 35...

Page 13: ...ENSATE DRAIN CONNECTION SUPPLY AIR INTERNAL CONDENSATE TRAY THE TOP OF THE P TRAP MUST BE 50MM BELOW THE TOP OF THE CONDENSATE DRAIN CONNECTION THE TOP OF THE P TRAP MUST BE 50MM BELOW THE TOP OF THE CONDENSATE DRAIN CONNECTION INSTALL A T PIECE AS AN AIR VENT FOR LONG DRAIN RUNS CLEAR PLASTIC INSPECTION TUBE P V C ELBOW CLAMP BANDS SEAL WITH SILICONE SEALANT PREFERRED METHOD OF CONNECTING P TRAP ...

Page 14: ...RT INCLUSIONS 8Z 24V 8 ZONE KIT 8Z 24V ZONE MODULE INSTALLATION INSTRUCTIONS Duct Duct Zone Barrel Damper Motor on Top of the Zone Barrel TYPE 10 250 mm PART NUMBER ZB 10 250 INTEGRATED ZONE BARREL PART NUMBERS 12 300 mm ZB 12 300 INTEGRATED ZONE BARRELS 12 300 mm 10 250 mm 16 400 mm 14 350 mm 14 350 mm 16 400 mm ZB 14 350 ZB 16 400 ITEM PART NUMBER 24 VOLT 4 ZONE KIT 4Z 24V INCLUSIONS 5 YEAR RESI...

Page 15: ...CABLE POWER ONLY YELLOW CAT5E CABLE MASTER SECONDARY OPTIONAL WiFi WiFi RF RF MODULATION ZONING QUEIB DATA ZONE 8 ZONE 7 ZONE 6 ZONE 5 ZONE 4 ZONE 3 ZONE 2 ZONE 1 TO ZONE 2 8 240V MAINS ZONE MOTOR ZONE CONTROL 1 REMOTE SENSOR 1 LOG RJ45 SOCKETS FOR ACTRON AIR CAT5E SPEC CABLES ONLY REFER TO QUE CONTROL SYSTEM INSTALLATION COMMISSIONING MANUAL FOR ALL AVAILABLE CONFIGURATIONS FIELD WIRING RF RF OPT...

Page 16: ... 410A 1 MODEL R 410A CAUTION PLEASE THERE IS NO GAS PRESSURE IN THE FAN COIL UNIT BEFORE REMOVING COPPER END CAPS ENSURE 3670 043 Sensor 4 CAUTION LIVE ELECTRICAL WIRING AUTHORISED TECHNICIANS ONLY INTERNAL CONTROL ISOLATOR FITTED MODEL MEPS CERTIFIED A U S TRALIAN M A D E A U STRALIAN OW N E D R 410A INDOOR UNIT 2 8 ZONE MODULE 3 TO INDOOR PCB Master Controller Item Description Maximum Cable Leng...

Page 17: ...OXED FOR SAFE TRANSPORT INCLUSIONS 8Z 24V 8 ZONE KIT 8Z 24V ZONE MODULE INSTALLATION INSTRUCTIONS MOUNTING SCREWS ITEM PART NUMBER 7 METER CABLE 4070 004 ZONE MOTOR ONLY TRANSFORMER ONLY ZM 24V 2045 046 20 METER CABLE 4070 007 2 WAY RJ45 JOINER 2045 121 3 WAY RJ45 JOINER 4070 008 ZONE OPTION 2 1 5V AAA 1 5V AAA 1 5V AAA 1 5V AAA TYPE 10 250 mm PART NUMBER ZB 10 250 INTEGRATED ZONE BARREL PART NUMB...

Page 18: ...mage rust and dust accumulation For highly corrosive environment wash panels quarterly with water and neutral detergent solution Wax panels Repair re paint where required Insulation Visual check for insulation conditions Repair replace insulation material Fan Visual check for run out of balance and dust attached Clean off dust as necessary to negate possibility of fan running out of balance Motor ...

Page 19: ...3 18AS ERQ5 21AS ERQ5 24AS Item Description Part Number Quantity Quantity Quantity Quantity 1 EC ID Fan 2520 330 1 1 EC ID Fan 2520 334 1 EC ID Fan 2520 313 1 2 Indoor Coil Assembly 1040 254 1 1 Indoor Coil Assembly 1040 274 1 Indoor Coil Assembly 1040 273 1 3 Coil Piston 4540 090 1 Coil Piston 4540 128 1 1 1 4 ID PC Board 2020 167 1 1 1 1 5 Zone Module 8Z VAQ 1 1 1 1 6 Filter Board 4080 013 1 1 7...

Page 20: ...pyright 2018 Actron Engineering Pty Limited ABN 34 002767240 Registered Trade Marks of Actron Engineering Pty Limited Document 0525 061 Ver 1 Issue Date 01 2019 Refrigerant Trading Authorisation No AU06394 ...

Reviews: