12 - 75
12. OPTIONS AND AUXILIARY EQUIPMENT
Table 12.4 Servo motor’s leakage current example (Igm)
Table 12.5 Servo amplifier's leakage current example (Iga)
Servo motor power
[kW]
Leakage current
[mA]
Servo amplifier capacity
[kW]
Leakage current
[mA]
0.05 to 1
0.1
0.1 to 0.6
0.1
2
0.2
0.75 to 3.5 (Note)
0.15
3.5 0.3
5 7 2
5 0.5
11 15 5.5
7 0.7
22 7
11 1.0
15 1.3
Note. For the 3.5kW of 400V class, leakage current is 2mA,
which is the same as for 5kW and 7kW.
22 2.3
Table 12.6 Leakage circuit breaker selection example
Servo amplifier
Rated sensitivity current of leakage
circuit breaker [mA]
MR-J3-10A to MR-J3-350A
MR-J3-10A1 to MR-J3-40A1
15
MR-J3-500A(4) 30
MR-J3-700A(4) 50
MR-J3-11KA(4) to MR-J3-22KA(4)
100
(2) Selection example
Indicated below is an example of selecting a leakage current breaker under the following conditions:
M
NV
Ig1
Iga
Ig2
Igm
Servo
amplifier
MR-J3-40A
2mm
2
5m
2mm
2
5m
Servo motor
HF-KP43
Use a leakage current breaker generally available.
Find the terms of Equation (12.2) from the diagram:
Ig1 20
1000
5
0.1 [mA]
Ig2 20
1000
5
0.1 [mA]
Ign 0 (not used)
Iga 0.1 [mA]
Igm 0.1 [mA]
Insert these values in Equation (12.2):
Ig 10 {0.1 0 0.1 1 (0.1 0.1)}
4.0 [mA]
According to the result of calculation, use a leakage current breaker having the rated sensitivity current (Ig)
of 4.0[mA] or more. A leakage current breaker having Ig of 15[mA] is used with the NV-SP/SW/CP/CW/HW
series.