3 - 45
3. SIGNALS AND WIRING
(b) Speed selection 1(SP1)/speed selection 2(SP2)/speed selection 3(SP3) and speed limit values
Choose any of the speed settings made by the internal speed limits 1 to 7 using speed selection
1(SP1), speed selection 2(SP2) and speed selection 3(SP3) or the speed setting made by the speed
limit command (VLA), as indicated below.
(Note) Input signals
SP3 SP2 SP1
Speed limit value
0 0 0
Analog
speed
limit
(VLA)
0 0 1
Internal
speed
limit
1
(parameter
No.
PC05)
0 1 0
Internal
speed
limit
2
(parameter
No.
PC06)
0 1 1
Internal
speed
limit
3
(parameter
No.
PC07)
1 0 0
Internal
speed
limit
4
(parameter
No.
PC08)
1 0 1
Internal
speed
limit
5
(parameter
No.
PC09)
1 1 0
Internal
speed
limit
6
(parameter
No.
PC10)
1 1 1
Internal
speed
limit
7
(parameter
No.
PC11)
Note. 0: off
1: on
When the internal speed limits 1 to 7 are used to command the speed, the speed does not vary with
the ambient temperature.
(c) Limiting speed (VLC)
VLC turns on when the servo motor speed reaches the speed limited using any of the internal speed
limits 1 to 7 or the analog speed limit (VLA).