9 - 2
9. TROUBLESHOOTING
9.2 Remedies for alarms
CAUTION
When any alarm has occurred, eliminate its cause, ensure safety, then reset the
alarm, and restart operation. Otherwise, injury may occur.
If an absolute position erase (AL.25) occurred, always make home position setting
again. Otherwise, misoperation may occur.
As soon as an alarm occurs, turn off Servo-on (SON) and power off.
POINT
When any of the following alarms has occurred, do not deactivate the alarm and
resume operation repeatedly. To do so will cause the servo amplifier/servo motor
to fail. Remove the cause of occurrence, and leave a cooling time of more than 30
minutes before resuming operation.
Regenerative error (AL.30)
Overload 1 (AL.50)
Overload 2 (AL.51)
The alarm can be deactivated by switching power off, then on press the "SET"
button on the current alarm screen or by turning on the reset (RES). For details,
refer to section 9.1.
When an alarm occurs, the trouble (ALM) switches off and the dynamic brake is operated to stop the
servomotor. At this time, the display indicates the alarm No.
The servo motor comes to a stop. Remove the cause of the alarm in accordance with this section. The optional
MR Configurator may be used to refer to the cause.
Display Name
Definition
Cause
Action
1. Power supply voltage is low.
2. There was an instantaneous
control power failure of 60ms or
longer.
3. Shortage of power supply capacity
caused the power supply voltage to
drop at start, etc.
4. The bus voltage dropped to the
following value or less.
MR-J3- A: 200VDC
MR-J3- A1: 158VDC
MR-J3- A4: 380VDC
Review the power supply.
AL.10 Undervoltage Power
supply
voltage dropped.
MR-J3- A:
160VAC or less
MR-J3- A1:
83VAC or less
MR-J3- A4:
280VAC or less
5. Faulty parts in the servo amplifier
Checking method
Alarm (AL.10) occurs if power is
switched on after disconnection
of all cables but the control
circuit power supply cables.
Change the servo amplifier.
AL.12 Memory
error
1
(RAM)
RAM, memory fault
AL.13
Clock error
Printed board fault
Faulty parts in the servo amplifier
Checking method
Alarm (any of AL.12 and AL.13)
occurs if power is switched on
after disconnection of all cables
but the control circuit power
supply cables.
Change the servo amplifier.