14 - 13
14. ABSOLUTE POSITION DETECTION SYSTEM
3) ABS transfer mode finish-time time-out check
If the ABS transfer mode (ABSR) is not turned OFF within 5s after the last ready to send signal (19th
signal for ABS data transmission) is turned ON, it is regarded as the transmission error and the ABS
time-out warning (AL.E5) is output.
OFF
ON
OFF
ON
OFF
ON
1
2
3
4
18
19
1
2
3
4
18
19
5s
ABS transfer mode
ABS request
ABS transmission
data ready
AL.E5 warning
Signal is not turned OFF
No
Yes
(b) Check sum error
If the check sum error occurs, the programmable controller should retry transmission of the ABS data.
Using the ladder check program, turn OFF the ABS transfer mode (ABSM) and servo-on (SON) once.
Turn them ON again after an OFF time of longer than 20 ms.
If the ABS data transmission fails to end normally even after retry, regard this situation as an ABS check
sum error and execute error processing.
The start command should be interlocked with the ABS data ready signal to disable positioning
operation when an check sum error occurs.
OFF
ON
OFF
ON
OFF
ON
OFF
ON
Servo-on
ABS transfer mode
ABS request
ABS transmission
data ready
ABS check sum error
20ms
or more
20ms
or more
20ms
or more
Retry 1
Retry 2
Retry 3
No
Yes