MI 3101 EurotestAT:
Technical specifications
91
8.2 Continuity
8.2.1 Resistance R200mA (LPE, NPE)
Measuring range according to EN61557 is 0.16
1999
.
Measuring range R (
) Resolution
(
)
Accuracy
0.00
19.99
0.01
(3 % of r 3 digits)
20.0
199.9
0.1
200
1999
1
(5 % of reading)
2000
9999
1 Indicator
only
Measuring range R+, R- (
) Resolution
(
)
Accuracy
0.00
19.9
0.1
(5 % of r 5 digits)
20.0
199.9
0.1
200
1999
1
(10 % of reading)
2000
9999
1 Indicator
only
Open-circuit voltage.......................... 6.5 VDC
9 VDC
Measuring current............................. min. 200 mA into load resistance of 2
Test lead compensation.................... up to 20
The number of possible tests ........... > 2000, with a fully charged battery
Automatic polarity reversal of the test voltage.
8.2.2 Resistance R7mA (LPE, NPE)
Measuring range (
) Resolution
(
)
Accuracy
0.0
19.9
0.1
20
1999
1
(5 % of r 3 digits)
2000
9999
1
Indicator only
Open-circuit voltage.......................... 6.5 VDC
9 VDC
Short-circuit current .......................... max. 8.5 mA
Test lead compensation.................... up to 20
8.3 RCD testing
8.3.1 General data
Nominal residual current (A,AC) ....... 10 mA, 30 mA, 100 mA, 300 mA, 500 mA,
1000 mA
Nominal residual current accuracy.... -0 / +0.1
I
; I
= I
N, 2
I
N, 5
I
N
-0.1
I
/ +0; I
= 0.5
I
N
AS / NZ selected: ± 5 %
Test current shape............................ Sine-wave (AC), pulsed (A),DC (B)
DC offset for pulsed test current ....... 6 mA (typical)
RCD type .......................................... G (non-delayed), S (time-delayed)
Test current starting polarity ............. 0 º or 180 º
Voltage range ................................... 40 V
264 V (14 Hz
500 Hz)