MI 3101 EurotestAT: Instrument operation
Miscellaneous
41
Keys:
TEST
Restores default settings.
ESC
Exits the menu without changes.
F2
Opens other settings menu.
Warning:
Custom made settings will be lost when this option is used!
The default setup is listed below:
Instrument setting
Default value
Contrast
As defined and stored by adjustment procedure
Isc factor
1.00
Supply system
TN / TT
RCD standards
EN 61008 / EN 61009
COM port
RS 232
Language English
Function
Sub-function
Parameter / limit value
CONTINUITY
R 200 mA
R LOW
High limit resistance value: OFF
Continuity
High limit resistance value: OFF
INSULATION
Nominal test voltage: 500 V
Low limit resistance value: OFF
Selected test leads combination: LN
Z - LINE
Fuse type: none selected
Δ
U Limit:
4.0
%
Z
ref
: 0.00
Ω
Z - LOOP
Protection: Fuse
Fuse type: none selected
2
line/loop impedance
m
L-N Fuse type: none selected
RCD RCD
t
Nominal differential current: I
N
=30 mA
RCD type: G
Test current starting polarity:
(0
)
Limit contact voltage: 50 V
Current multiplier:
1
Earth resistance
3-wire
3-wire
Limit value: OFF
Specific resistance
Distance unit: m
Varistor test
Lo limit: 300 V
Hi limit: 400 V
Other settings
F2
Enters menu to unlock the protected auto sequences and comments and/or
select distance unit for specific earth resistance measurement.