MI 3101 EurotestAT: Appendix H
DK modifications
136
Prospective fault current I
SC
is calculated from measured impedance as follows:
Z
k
Un
I
SC
SC
where:
Un ........Nominal U
L-PE
voltage (see table below),
ksc .......Correction factor for Isc (see chapter
4.4.2
).
U
n
Input voltage (L-PE)
110 V (93 V
U
L-PE
134 V)
230 V (185 V
U
L-PE
266 V)
Notes:
High fluctuations of mains voltage influence the measurement results. The noise
sign
is displayed in the message field in such case. Repeat the measurement.
Isc is not calculated in case the terminal voltage monitor does not detect voltage
state that corresponds to the selected supply system, indication
.
This measurement will trip-out RCD in RCD-protected electrical installation if Sikring
is selected as breaking device instead of RCD.