MI 3101 EurotestAT: Instrument operation
Automatic testing
35
(3 x)
4.3.7 Select
COMMENT:
#1.
TEST
4.3.7
Confirm selected pause and its comment.
4.3 Next
step.
/
4.3.2
Select
INSULATION.
TAB
4.3.2
Enter test parameter selection mode.
TEST
ALL
U
ISO
500
V
Limit
ON
Limit
1M
5.1
Setting test parameters for insulation resistance.
TAB
4.3.2
Exit parameter mode.
F1
4.3.2 Set
PAUSE
(wait to reconnect measuring leads).
/
4.3.7 Set
PAUSE:
ON.
4.3.7 Select
COMMENT.
(2 x)
4.3.7 Select
COMMENT:
#2.
TEST
4.3.7
Confirm selected pause and its comment.
4.3 Next
step.
/
4.3.2
Select
VOLTAGE.
F1
4.3.2 Set
PAUSE
(wait to connect mains voltage).
/
4.3.7 Set
PAUSE:
ON.
4.3.7 Select
COMMENT.
(3 x)
4.3.7 Select
COMMENT:
#3.
TEST
4.3.7
Confirm selected pause and its comment.
4.3 Next
step.
/
4.3.2
Select
Z-LINE.
TAB
4.3.2
Enter test parameter selection mode.
FUSE type
gG
FUSE I
6A
FUSE T
5s
5.5
Set test parameters for line impedance and fuse
test.
TAB
4.3.2
Exit parameter mode.
4.3 Next
step.
/
4.3.2
Select
RCD.
TAB
4.3.2
Enter test parameter selection mode.
TEST
Tripout current
Idn
30mA
type
G
Ulim
50V
5.3
Test parameters for RCD trip-out current test
(
results of this test are also contact voltage at I
and trip out time).
TAB
4.3.2
Exit parameter mode.
4.3 Next
step.
F1
4.3.2 Set
PAUSE
(wait to activate RCD).
/
4.3.7 Set
PAUSE:
ON.
4.3.7 Select
COMMENT.
(4 x)
4.3.7 Select
COMMENT:
#4.
TEST
4.3.7
Confirm selected pause and its comment.
/
4.3.2
Select
RCD.
TAB
4.3.2
Enter test parameter selection mode.
TEST
Tripout time t
Idn
30mA
type
G
MUL x5
Ulim
50V
5.3
Test parameters for RCD trip out time test at
5I
N
(
result of this test is also contact voltage at I
N
).