MI 3101 EurotestAT: Measurements
Varistor test
75
5.11 Varistor test
This test is performed to verify overvoltage protection devices. Typical devices are:
Metal oxide varistors,
Gas arresters,
Semiconductor transient voltage suppressors.
See chapter
4.2 Single test
for functionality of keys.
Figure 5.46: Varistor test menu
Test parameters for varistor test
Lo limit
Low limit
DC threshold voltage
[50 V ÷ 1000 V]
Hi limit
High limit
DC threshold voltage
[50 V ÷ 1000 V]
It = 1.00 mA
Threshold current
Test circuit for varistor test
L1
L2
L3
N
PE
mains voltage
switched off
opened
switches
N/
L
2
L
/L
1
PE
/L
3
permanent
loads
disconnected
Figure 5.47: Connection of universal test cable for varistor test