MI 3101 EurotestAT:
Technical specifications
98
U
N(L-PE)
= 230 V
10 %
230 V < U
N
< 400 V
C
MAX
1.05 1.10
C
MIN
0.95
1.00
8.9.3 Contact voltage
Measuring range (V)
Resolution (V)
Accuracy
0
100
1
(10 % + 3 digits)
8.10 Varistor test
DC voltage
Measuring range (V)
Resolution (V)
Accuracy
0
1000
1
(3 % of r 3 digits)
AC voltage
Measuring range (V)
Resolution (V)
Accuracy
0
625
1
Consider accuracy of DC voltage
Measurement principle...................... d.c. voltage ramp
Test voltage slope............................. 500 V/s
Threshold current.............................. 1 mA