MI 3101 EurotestAT: Appendix G
ES1 – application of regulative UNE-202008
127
Figure G.4: Examples of results
Markings:
...........Inspection was not performed
...........Inspection passed.
...........Inspection failed.
G.3.2 Resistance to earth connection and equipotential bonding
The resistance measurement is performed in order to assure that protective measures
against electric shock through earth bond connections are effective. Five subfunctions are
available:
Earth bond resistance measurement according to EN 61557-4 (between N and PE
terminals, test current >200 mA),
Earth bond resistance measurement according to EN 61557-4 (between L and PE
terminals, test current >200 mA),
Continuous resistance measurement with lower test current (between N and PE
terminals, test current ca 7 mA),
Continuous resistance measurement with lower test current (between L and PE
terminals, test current ca 7 mA), and
Resistance of PE conductor through fault loop measurement.