MI 3101 EurotestAT: Instrument operation
Automatic testing
26
4.3.1 Auto sequence number main menu
In the instrument up to 99 automatic sequences can be stored.
#3
Auto sequence number.
*
Indicator that the preset sequence was changed and is
not stored yet, the auto sequence can be performed
anyway.
TEST EXA1
Optional sequence name (see
4.3.4
).
Indication of locked sequence (see 4.3.2).
4.3.2 Auto sequence set
Keys in main auto sequence menu:
TEST
Starts the selected test sequence.
Enters / clears pause
II
before test.
/
Select the test sequence number or measuring function (see
4.3.1).
/
Select individual sequence step / measuring function.
TAB
Enters test parameter field (see
4.3.3).
ESC
Exits auto sequence menu without changes.
F1
Enters editor to rename selected test sequence and enter its description (see
4.3.4).
Enters menu for setting pause flag and comments (see
4.3.7)
.
F2
Saves entered test sequence (see
4.3.5).
MEM
Stores / recalls AUTO SEQUENCE results.
Function selection
Parameter selection
Figure 4.7: Example of setting auto sequence sequence
For each of 6 predefined sequence steps any of the following measurement function can
be selected: voltage, continuity, insulation, Zline, Zloop, RCD and earth. The field can also
be left empty (
- - -
).
Test parameters are applied to individual measurements as in the single test. The test
parameter menu of selected measurement is available on the right side of the display.
The
pause
II
flag holds the auto sequence until prosecution is confirmed with the
TEST
key. It is recommended to use it if additional checks or reconnections have to be
performed before performing the next measurement.