MI 3101 EurotestAT: Instrument operation
Automatic testing
27
The key is indication of locked sequence. This indication appears at predefined sequences
that were loaded into the instrument from PC. It is possible to modify locked auto
sequences and run them. However, the modified sequence cannot be stored by
overwriting.
Note:
It is recommended to save current auto sequence if modified or new prepared, to
keep it during manipulation.
4.3.3 Test parameters in auto sequence
Keys in test parameter menu (in auto sequence):
/
Select test parameter value or enable / disable parameter.
/
Select
test
parameter.
TEST, TAB, ESC
Return to auto sequence main screen.
Whenever a new function is selected for auto sequence its test parameters should be
verified and changed to appropriate values / states.
Test parameter merging
When the prepared sequence from
section 4.3.2
contains selected at least two of Zline,
Zloop, or RCD, is possible to merge test parameters of one function to others of mentioned
in the same sequence.
Merged parameters are related to:
- fuse
data,
and
- RCD data, except start polarity of test current.
Additional Key in main auto sequence menu with selected Zline, Zloop, or RCD:
F2
Merges test parameters.
Figure 4.8: Parameter merging possibility