MI 3101 EurotestAT: Measurements
Continuity
51
Circuits for compensating the resistance of test leads
N/L2
PE/L3
N/L2
PE/L3
extension lead
PE/L3
N/L2
Figure 5.11: Shorted test leads-examples for N-PE
Compensation of test leads resistance procedure
Select the
CONTINUITY
function (any).
Connect
test cable to the instrument and short N/PE or L/PE terminals (see figure
5.11
).
Press the
F1
key to open test leads resistance compensation menu.
Press the
TEST
key for measurement and compensation of test leads resistance.
Press the
ESC
key to return to function menu.
Note:
20
is limit value for test leads resistance compensation.