MI 3101 EurotestAT:
Technical specifications
92
RCD test current selection (r.m.s. value calculated to 20ms) according to IEC 61009:
I
N × 1/2
I
N × 1
I
N × 2
I
N × 5
RCD I
I
N (mA) AC
A B AC
A B AC
A B
AC
A
B AC
A
B
10
5 3.5
5 10 20 20 20 40 40
50 100
100
30
15
10.5
15 30 42 60 60 84 120 150 212
300
100
50 35 50 100 141 200 200 282 400 500 707
1000
300
150
105 150 300 424 600 600 848 n.a. 1500 n.a.
n.a.
500
250
175 250 500 707 1000 1000
1410 n.a. 2500 n.a.
n.a.
1000 500
350
500
1000
1410
n.a.
2000
n.a. n.a. n.a. n.a.
n.a.
n.a.
n.a..................................................... not applicable
8.3.2 Contact voltage RCD-Uc
Measuring range according to EN61557 is 20.0 V
31.0V for limit contact voltage 25V
Measuring range according to EN61557 is 20.0 V
62.0V for limit contact voltage 50V
Measuring range (V)
Resolution (V)
Accuracy
0.0
19.9
0.1
(-0 % / +15 %) of reading ± 10 digits
20.0
99.9
(-0 % / +15 %) of reading
The accuracy is valid if mains voltage is stabile during the measurement and PE terminal
is free of interfering voltages.
Test current....................................... max. 0.5
I
N
Limit contact voltage ......................... 25 V, 50 V
Specified accuracy is valid for complete operating range.
8.3.3 Trip-out time
Complete measurement range corresponds to EN 61557 requirements.
Maximum measuring times set according to selected reference for RCD testing.
Measuring range (ms)
Resolution (ms)
Accuracy
0.0
40.0
0.1
1 ms
0.0
max. time *
0.1
3 ms
* For max. time see normative references in
4.4.2
– this specification applies to max. time
>40 ms.
Test current....................................... ½
I
N
, I
N
, 2
I
N
, 5
I
N
5
I
N
is not available for I
N
=1000 mA (RCD types AC) or I
N
300 mA (RCD type A,B).
2
I
N
is not available for I
N
=1000 mA (RCD type A,B).
1
I
N
is not available I
N
=1000 mA (RCD Typ B).