MI 3101 EurotestAT: Instrument operation
Automatic testing
24
4.3 Automatic testing
is intended for automatic executing of predefined measurement sequences.
Figure 4.3: Typical auto
sequence screen
Auto sequence menu.
Selected sequence number
and (optional) name.
Sequence field.
Test parameter / auto
sequence description field.
Saving and renaming options.
Running auto sequence:
Select auto sequence (see
4.3.2
).
Connect the instrument to tested object as required for the first measurement in the
sequence.
Press TEST key.
The sequence will pause at the functions marked with pause flag
II
. Comments
regarding the paused function will be displayed (optional).
♦
Press the TAB key to toggle between comments menu and auto sequence main
menu.
♦
If the conditions at input terminals are valid, the test will proceed after pressing
the TEST key.
♦
Press the F1 key to skip the paused function. The test will continue with the
next test (if any) or will end.
♦
Press the ESC key to skip the remaining functions and finish the auto
sequence.
The set of measurements will be performed in sequential manner until the
conditions at input terminals are valid for each individual test. If not, the instrument
will stop (the buzzer sounds). The auto sequence will proceed:
♦
After correct conditions are restored at the input terminal (e.g. by reconnecting,
switching on the RCD).
♦
If pressing the F1 key this function will be skipped.
♦
By pressing the ESC key to skip the remaining functions and finish the auto
sequence.
Results of a finished auto sequence can be viewed and stored. See chapter
6.
for
more information.