MI 3101 EurotestAT: Appendix G
ES1 – application of regulative UNE-202008
129
G.3.2.3 R-PE(loop) measurement
It is based on Z-Loop measurement which also gives reference value measured at e.g.
switchboard or common coupling point of tested electrical installation.
Test circuit for R-PE(loop) measurement
L1
L2
L3
N
PE
R
E
Ro
L
PE
N
L/L1
N/L2
PE/L3
L/L1
N/L2
PE/L3
1
Figure G.6: Connection for reference (1) and socket measurements
R-PE(loop) measurement procedure
(For reference measurement procedure see chapter
G.3.3 Fault loop impedance and
prospective fault current
)
Select the
CONTINUITY
function.
Set sub-function
R-PE(loop)
.
Enable and select
Fuse I
(optional).
Select maximum
touch voltage Uc
(optional).
Connect
test cable to the instrument.
Tested installation must be in normal operating condition with mains supply.
Connect
test leads to the tested socket (see
figure
G.6
).
Press the
TEST
key for measurement.
After the measurement is finished
store
the result (optional).
Figure G.7: Example of continuity R-PE(loop) result