5-23
Symptom
Content of the likely cause
Countermeasures
Reference
Unable to run/set
with Modbus
communication.
The changes on the communication
parameter are not reflected.
If the communication transmission speed selection
(C071), communication parity selection (C074), or
communication stop bit selection (C075) were
changed, restart the power or reset (Turn ON then
OFF on the RS terminal).
The primary/secondary run command
selection (A002/A202) is incorrect.
Set the primary/secondary run command selection
(A002/A202) to “03: Modbus communication”.
The primary/secondary frequency
command selection (A001/A201) is
incorrect.
Set the primary/secondary frequency command
selection (A001/A201) to “03: Modbus
communication”.
The communication speed setting is
incorrect.
Set the correct communication speed on the
communication transmission speed selection
(C071).
The station number setting is incorrect.
Or is overlapping.
Set the correct station number on the
communication station number selection (C072).
The communication parity setting is
incorrect.
Set the correct communication parity on the
communication parity selection (C074).
The communication stop bit setting is
incorrect.
Set the correct stop bit on the communication stop
bit selection (C075).
Incorrect wiring.
Route the wires properly to the RS+, RS-
terminal of the control circuit terminal block.
Incorrect address.
• Check that the coil address and register address
are correct, and that the value “
−
1” from the
register number is set.
• If the Modbus mapping function is being used,
check that the setting is correct, and fix
accordingly.
The circuit breaker
activates when
running the
inverter.
The leakage current of the inverter is
large.
Reduce the carrier frequency (b083).
Raise the sensitive current of the leakage breaker.
Or replace with circuit breaker with higher sensitive
current.
DC breaking does
not operate.
The DC breaking has not been set.
Set the DC breaking (A054).
The DC breaking time has not been set.
Set the DC breaking time (A055).
Trips with
insufficient voltage
(E09).
Voltage drop due to insufficient power
capacity.
Raise the power capacity.
Noise is observed
on television sets
and radio near the
inverter.
Noise emitted from the inverter.
Place the cables of the inverter as far as possible
from the television set and radio.
Optional units fault
(E60 to E68)
occurs.
The optional units detected a failure
and reported them.
Refer to the manuals of the optional units.
Inverter failure; the optional unit
connector is not operating normally.
If the issue cannot be solved on the optional unit
side, it may be a failure. If the issue cannot be
solved after checking the bad linkage and
contamination of the connection part, replace the
inverter.
Optional units fault
(E69) occurs.
Communication cannot be carried out
after the optional unit has been
detected. Optional unit may be loose.
Check for bad linkage, contamination of the
connection part of the optional unit connector.
Check that the terminal block cover of the inverter
and the cover of the optional unit are properly
linked, and that the screws are properly installed.
The endian function of the Modbus
mapping function is set improperly.
Set Modbus mapping endian selection (P400) to
“00: big endian”.
Summary of Contents for MK0003
Page 2: ......
Page 8: ...0 6...
Page 12: ...1 4 2 DIMENSIONAL DRAWING OF OUTRIGGER WIDTH...
Page 17: ...1 9 4 WORKING RADIUS LIFTING HEIGHT...
Page 18: ...1 10 Working range diagram Outrigger extended to maximum Main boom 1 section...
Page 19: ...1 11 Working range diagram Outrigger extended to maximum Main boom 2 sections...
Page 20: ...1 12 Working range diagram Outrigger extended to maximum Main boom 2 5 sections...
Page 21: ...1 13 Working range diagram Outrigger extended to maximum Main boom 3 sections...
Page 22: ...1 14 Working range diagram Outrigger extended to minimum Main boom 1 section...
Page 23: ...1 15 Working range diagram Outrigger extended to minimum Main boom 2 sections...
Page 24: ...1 16 Working range diagram Outrigger extended to minimum Main boom 2 5 sections...
Page 25: ...1 17 Working range diagram Outrigger extended to minimum Main boom 3 sections...
Page 26: ...1 18 5 RATED TOTAL LOAD CHART...
Page 32: ...2 4...
Page 33: ...2 5 1 HYDRAULIC CIRCUIT DIAGRAM 200 1176600...
Page 34: ...2 6...
Page 35: ...2 7 2 HYDRAULIC PIPING DIAGRAM 2 1 CRANE ROTATING PART 200 1171800...
Page 41: ...2 13 2 2 CONTROL LINE A...
Page 43: ...2 15 2 3CONTROL LINE B Perform spiral winding on the entire perimeter of the hose of this part...
Page 45: ...2 17 2 4 TRAVEL LINE...
Page 47: ...2 19 2 5 OUTRIGGER LINE...
Page 49: ...2 21 2 6 PT LINE 102 1152000 4...
Page 69: ...2 41...
Page 70: ...2 42...
Page 71: ...2 43...
Page 76: ...2 48 4 8 ENGINE ACCESSORIES 102 1149200...
Page 90: ...2 62 7 2 INTERNAL STRUCTURE...
Page 120: ...2 92 Part B Writing method for wire number Two places...
Page 123: ...2 95 Figure 1 Index point Figure 2 Connection diagram...
Page 166: ...2 138 15 4 APPEARANCE OF OUTRIGGER ON REAR LEFT SIDE 200 2167300...
Page 173: ...2 145 17 ELECTRIC CIRCUIT DIAGRAM 200 1176500 01...
Page 174: ...2 146 18 ELECTRIC SYSTEM 18 1 1 WIRE HARNESS OF MACHINE BODY 1 200 1172200 1...
Page 176: ...2 148 18 1 2 WIRE HARNESS OF MACHINE BODY 2 200 1172200 2...
Page 179: ...2 151 19 CONTROL ASSEMBLY 19 1 CONTROLLER 1 TTC60 Pin arrangement...
Page 180: ...2 152 TTC60 I O...
Page 181: ...2 153 2 TTC36X Pin arrangement...
Page 182: ...2 154 TTC36X lower part I O...
Page 209: ...2 181 19 2 5 LIST OF CONTROLLER INPUT MONITORING...
Page 210: ...2 182 19 2 6 LIST OF CONTROLLER ANALOG INPUT OUTPUT MONITORING...
Page 245: ...3 9 1 2 3 ANGLE METER 360 S200M3297000...
Page 274: ...3 38...
Page 293: ...4 19 8 SERVICE LOCATIONS...
Page 294: ...4 20...
Page 296: ...5 2 1 ELECTRICAL MOTOR UNIT ASSEMBLY Unit weight 180 kg...
Page 324: ...5 30...
Page 325: ...5 31 4 ELECTRICAL DIAGRAM S200M3122000 01...
Page 326: ...5 32 S200M3122000 02...
Page 336: ...6 8 1 3 2 INTERNAL STRUCTURE OF WINCH MOTOR...
Page 345: ...6 17 4 WORKING RADIUS LIFTING HEIGHT OF ONE FALL WINCH...
Page 348: ......