2
Issue 1.0
August 1998
363-208-010 Appendix 2
NE00676-70 Local Alarm Relay Unit Installation Procedure
Support
If any of the steps specified in this procedure cannot be completed as indicated,
call the next level of support or the Lucent Technologies Regional Technical Assis-
tance Center (RTAC) by the following phone number for assistance.
RTAC: 1-800-CAL RTAC (225-7822)
Training
No specific training is required.
Time Estimates
If LARU only is being installed:
a. Overall time to perform this procedure is estimated to be one half hour.
b. There will be no time out-of-service during this procedure.
c. One installer or craftsperson is recommended for this procedure.
If LARU and 404B UIP is being installed:
a. Overall time to perform this procedure is estimated to be one hour.
b. There will be no time out-of-service during this procedure.
c. Two installers or craftspersons are recommended for this procedure.
Risk Assessment
Procedural Risk Assessment
Rating (LARU only):
LOW
Since the installation of the LARU does not impact transmission this
procedure has a LOW procedural risk rating, since there is NO potential
for a service interruption to the end customer, if any procedural deviations
or procedure specific equipment failures occur during the procedure.
Summary of Contents for SLC-2000 Access System Central Office Terminal
Page 1: ...SLC 2000 Access System Customer Assembly Manual for RT Frames 363 208 010 Issue 5 May 1997...
Page 4: ...This page is intentionally blank...
Page 10: ...viii Issue 5 May 1997 Contents...
Page 16: ...xiv Issue 5 May 1997 Tables...
Page 24: ...1 ii Issue 5 May 1997 Contents General Information...
Page 34: ...2 iv Issue 5 May 1997 Tables Installation Procedures 2 1 Dimensions for Figure 2 2 6...
Page 66: ...3 viii Issue 5 May 1997 Contents Cabling Wiring and Assembly...