3-36
Issue 5
May 1997
363-208-010
Cabling, Wiring, and Assembly
Connections
Step 1:
Locate the ED7C723-34 Group 2() Cable Assembly J303/P303 connec-
tor interface at the ARM Shelf. This cable is part of the PIU. Cut any ties
as required to gain access to these connectors.
Step 2:
Disconnect this ARM shelf connection and install the ED7C723-34
Group 5 Cable Assembly as follows:
a. Mate the P303 connector on the cable to the ARM shelf's J303 con-
nector.
b. Mate the J303 connector on the cable to the PIU cable's (Group 2)
P303 connector.
c. Mate the J190-1 connector on the cable to the first HDOS P190 con-
nector.
d. Mate the J190-2 connector on the cable to the second HDOS P190
connector. If the second HDOS is not provided at this time leave the
J190-2 connector visible in the area of the future shelf.
e. Leave the J190-3 connector on the cable visible in the area of a
future third HDOS (above the other HDOS).
f. Mate the J114 connector on the cable to the Fan Shelf's P114 con-
nector.
Step 3:
Secure the cable assembly to the PIU's cable assembly wherever possi-
ble but leaving enough slack to reach the future HDOS positions.
Summary of Contents for SLC-2000 Access System Central Office Terminal
Page 1: ...SLC 2000 Access System Customer Assembly Manual for RT Frames 363 208 010 Issue 5 May 1997...
Page 4: ...This page is intentionally blank...
Page 10: ...viii Issue 5 May 1997 Contents...
Page 16: ...xiv Issue 5 May 1997 Tables...
Page 24: ...1 ii Issue 5 May 1997 Contents General Information...
Page 34: ...2 iv Issue 5 May 1997 Tables Installation Procedures 2 1 Dimensions for Figure 2 2 6...
Page 66: ...3 viii Issue 5 May 1997 Contents Cabling Wiring and Assembly...