2-10
Issue 5
May 1997
363-208-010
Installation Procedures
Figure 2-4. Grounding Connections
Join 54720 (Thomas & Betts)
Compression "C" Tap To Ring Ground Wire
See Note And Figure A And/Or Figure B
No. 2 AWG
Stranded Wire
Ring Ground
Bay Framework
Provided With Bay Frame
The "C" Type Tap Shall Always Turn
In The Direction Of The Closest
Ring Bus Bond.
Note:
54740 Compression C Tap
(Thomas & Betts) 2 Required
No. 6 AWG
Stranded Wire
No. 2 AWG Solid
Ring Ground
Figure B
Crimp Connector For Assembly For
No. 2 Or No. 6 AWG
Stranded To Solid Copper Wire
54720 Compression C
Tap (997775952)
(Thomas & Betts)
No. 2 AWG Stranded
Ring Ground Wire
No. 6 AWG Stranded
Ring Ground Wire
Figure A
Crimp Connector Assembly For
No. 2 Or No. 6 AWG
Stranded To Stranded Wire
Part Of Cable Rack
(Front View)