81
5
Functional Description with Process Diagrams
5.1.2
Default Process Flow for Gas Modulating Without Pilot Burner
Fig. 5-3 Process sequence chart for gas modulating without pilot burner
Signal bar
Significant times and their parameters
Standard
Signal must be present.
t4*
Parasitic light monitoring time
P803
5.0 s
Signal must not be present.
t5
Pre-ventilation time
P318
1 - 999 s
Signal can be present.
t6
Transformer pre-activation time
P309
3.0 s
t7
1
st
safety time
P305
4.0 s
t11
Control release delay time
P380
0.0 s
t12
Block and bleed of the gas train
P334
3.0 s
t13
Post-ventilation time
P319
0.0 s
t22
Program monitoring time
P304
600 s
t23
Irrelevance time
P323
2.0 s
Summary of Contents for CMS
Page 2: ......
Page 131: ...130 7 Operating Control and Displays 7 1 5 5 Deleting Curves Delete firing rate curve...
Page 148: ...147 7 Operating Control and Displays Channel configuration AL1 Fig 7 18 Channel configuration...
Page 157: ...156 7 Operating Control and Displays Fig 7 27 System CRCs menu...
Page 162: ...161 7 Operating Control and Displays Fig 7 32 IP setting menu...
Page 166: ...165 7 Operating Control and Displays Fig 7 35 Installation...
Page 167: ...166 7 Operating Control and Displays Fig 7 36 Installation...
Page 176: ...175 7 Operating Control and Displays Fig 7 49 Loading a protected dataset into the device...
Page 202: ...201 7 Operating Control and Displays Replacing a Module Fig 7 81 Module replacement menu...
Page 276: ...275 10 Maintenance 3 Restart CMS to complete the update...
Page 282: ...281 12 Appendix 12 5 EU Declaration of Conformity...
Page 283: ...282 12 Appendix...