110
6
Commissioning
RC curves: programming the ignition point (AL1)
1. Click the ’Start configuration’ button.
2. Enter a password if required to do so.
3. Dialogue box: ’Start configuration with fan?’
If a fan is present, the fan must be activated for programming the curve.
Feedback would otherwise be absent.
4. Click button
.
This ensures that all points are deleted.
5. Use the arrow keys to program the ignition point as 2
nd
base firing rate point
.
6. Click button
.
All channels must reach their setpoint.
The setpoint must match the actual value.
All channels are always saved together.
7. Click the ’Exit configuration’ button and then start the burner.
8. If ignition is successful, go to RC curves again and ’Start configuration’, and adjust the ig-
nition point again or program the next base firing rate point.
9. If ignition failed (= burner OFF), adjust the ignition point:
First ’Start configuration’, then ’Exit configuration’ again and then start the burner.
Summary of Contents for CMS
Page 2: ......
Page 131: ...130 7 Operating Control and Displays 7 1 5 5 Deleting Curves Delete firing rate curve...
Page 148: ...147 7 Operating Control and Displays Channel configuration AL1 Fig 7 18 Channel configuration...
Page 157: ...156 7 Operating Control and Displays Fig 7 27 System CRCs menu...
Page 162: ...161 7 Operating Control and Displays Fig 7 32 IP setting menu...
Page 166: ...165 7 Operating Control and Displays Fig 7 35 Installation...
Page 167: ...166 7 Operating Control and Displays Fig 7 36 Installation...
Page 176: ...175 7 Operating Control and Displays Fig 7 49 Loading a protected dataset into the device...
Page 202: ...201 7 Operating Control and Displays Replacing a Module Fig 7 81 Module replacement menu...
Page 276: ...275 10 Maintenance 3 Restart CMS to complete the update...
Page 282: ...281 12 Appendix 12 5 EU Declaration of Conformity...
Page 283: ...282 12 Appendix...