Faults
No.
Description
D1
D2
Extra
384
Internal fault
– Reset fault
– If the fault still exists:
Send fault number and diagnostic code to the
technical support.
– Replace the device
Required action
0
R = 0
Power ON Reset
385
Inconsistent values between main processor and
watchdog processor
Fault in an internal self-test.The digital input signals
for main and watchdog processor are compared and
are not the same.
– Reset fault and switch mains OFF and ON again if
necessary
– Check all fuses in the device. A bouncing signal
can cause different states to be detected between
the main processor and the watchdog processor.
– The main processor and the watchdog processor
detect the digital input signals at slightly different
times. A signal change only occurs so briefly that
the main processor detects it, but the watchdog
processor does not.
– Check signal sequence
– Reset error
– If the fault still exists:
Transfer fault number and diagnostic code to the
technical support
Firing rate at
which it is to be
programmed
Index at which it is
to be programmed
R = 0
Power ON Reset
386
Inconsistent values in SETTING mode
– Reset fault
– If the fault still exists:
Transfer fault number and diagnosis code
to the technical support.
– Replace the device.
0
0
R = 0
Power ON Reset
387
Internal fault
– Reset fault
– If the fault still exists:
Send fault number and diagnostic code to the
technical support.
– Replace the device
388 - 392 Internal fault
– Reset fault
– If the fault still exists:
Send fault number and diagnostic code to the
technical support.
– Replace the device
400
Permanent air deficiency
The air deficiency cannot be corrected by counter-
measures.
– Reset fault.
– If the fault still exists:
Transfer fault number and diagnosis code to the
technical support.
– Replace device
0
0
R = 0, 0, 0, 0
Reset
Summary of Contents for CMS
Page 2: ......
Page 131: ...130 7 Operating Control and Displays 7 1 5 5 Deleting Curves Delete firing rate curve...
Page 148: ...147 7 Operating Control and Displays Channel configuration AL1 Fig 7 18 Channel configuration...
Page 157: ...156 7 Operating Control and Displays Fig 7 27 System CRCs menu...
Page 162: ...161 7 Operating Control and Displays Fig 7 32 IP setting menu...
Page 166: ...165 7 Operating Control and Displays Fig 7 35 Installation...
Page 167: ...166 7 Operating Control and Displays Fig 7 36 Installation...
Page 176: ...175 7 Operating Control and Displays Fig 7 49 Loading a protected dataset into the device...
Page 202: ...201 7 Operating Control and Displays Replacing a Module Fig 7 81 Module replacement menu...
Page 276: ...275 10 Maintenance 3 Restart CMS to complete the update...
Page 282: ...281 12 Appendix 12 5 EU Declaration of Conformity...
Page 283: ...282 12 Appendix...