104
5
Functional Description with Process Diagrams
5.4.3.2 I Term
The firing rate controller can use an actual current value (mA), the boiler temperature (°C, °F)
or the steam pressure (bar, psi) as the actual value for control. P 61 defines the unit of the
actual value.
For steam pressure, P 62 and P 63 are also required.
5.4.3.3 Constant Controller
If the firing rate controller is used as a constant control, its setpoint is obtained from the pa-
rameters
•
P 49 for setpoint 1
•
P 51 for setpoint 2
P no.
Description
Attributes
61
Selection of the actual value input and the unit for indication (0-Digit; 1-°C; 2-bar; 3-mA; 4-
°F; 5-psi)
V1.0.0.0
Selection of the unit in which the input for actual value is to be indicated
0 = Digit
1 = °C
2 = bar
3 = mA
4 = °F
5 = psi
Write: 0/GUI/UI
Read: 0
Default: 2
Min: 0
Max:5
62
Pressure input: Scaling minimum
V1.0.0.0
Pressure at 4 mA input current in 0,1 units (bar, psi).
Input of the lower limit of the display range, which corresponds to 4 mA at the input, if the
input is configured as pressure input.
This parameter can only be active if P 61 = 2
Example: Value = 100, is equal to a minimum pressure of 10,0 bar/psi
Write: 1/GUI/UI
Read: 0
Default: 0
Min: 0
Max:999
63
Scaling maximum
V1.0.0.0
Pressure at 20 mA input current in 0,1 units (bar, psi).
Input of the upper limit of the display range, which corresponds to 20 mA at the input, if the
input is configured as pressure input. This parameter can only be active if P 61 = 2
Example: Value= 500, is equal to a maximum pressure of 50,0 bar/psi
Write: 1/GUI/UI
Read: 0
Default: 160
Min: 0
Max: 999
P no.
Description
Attributes
49
Controller 1 maximum value (only for control by atmospheric conditions)
V1.0.0.0
Controller setpoint 1 max. for control by atmospheric conditions
Enter the setpoint maximum for the controller in °C or bar. The setting is active if the input
"Setpoint changeover" = 0.
Write 0/GUI/UI
Read: 0
Default: 84
Min: -32768
Max: 32767
51
Controller 2 maximum value (only for control by atmospheric conditions)
V1.0.0.0
Controller setpoint 2 maximum for control by atmospheric conditions
Enter the setpoint maximum for the controller in °C or bar. The setting is active if the input
"Setpoint changeover" = 1.
Write: 0/GUI/UI
Read: 0
Default: 84
Min: -32768
Max: 32767
Summary of Contents for CMS
Page 2: ......
Page 131: ...130 7 Operating Control and Displays 7 1 5 5 Deleting Curves Delete firing rate curve...
Page 148: ...147 7 Operating Control and Displays Channel configuration AL1 Fig 7 18 Channel configuration...
Page 157: ...156 7 Operating Control and Displays Fig 7 27 System CRCs menu...
Page 162: ...161 7 Operating Control and Displays Fig 7 32 IP setting menu...
Page 166: ...165 7 Operating Control and Displays Fig 7 35 Installation...
Page 167: ...166 7 Operating Control and Displays Fig 7 36 Installation...
Page 176: ...175 7 Operating Control and Displays Fig 7 49 Loading a protected dataset into the device...
Page 202: ...201 7 Operating Control and Displays Replacing a Module Fig 7 81 Module replacement menu...
Page 276: ...275 10 Maintenance 3 Restart CMS to complete the update...
Page 282: ...281 12 Appendix 12 5 EU Declaration of Conformity...
Page 283: ...282 12 Appendix...