237
8
CO/O
2
Control
Behaviour during CO detection
Fig. 8-29 Parameter CO- controller - Behaviour during CO detection
1
Increasing air: Initial value at upcoming CO detection [digit]
Number of optimisation points that raise the current correction signal in the direction
of excess air immediately after the CO threshold has been detected.
Factory setting and value range 0 ... 300 corresponds to 0 ... 300 digit.
2
Increasing air: Speed gradient after CO detection [digit/s]
Number of optimisation points that increase the current correction signal in the direc-
tion of excess air during a direction change of the firing rate.
Factory setting and value range 0 ... 400 corresponds to 0 ... 400 digit.
3
Decreasing air: (Falling) speed gradient after decreasing CO correction [digit/s]
After a completed optimisation, the correction signal leaves the associated optimisa-
tion point by the set number of digit in the direction of excess air.
Factory setting and value range 0 ... 200 corresponds to 0 ... 200 digit.
Summary of Contents for CMS
Page 2: ......
Page 131: ...130 7 Operating Control and Displays 7 1 5 5 Deleting Curves Delete firing rate curve...
Page 148: ...147 7 Operating Control and Displays Channel configuration AL1 Fig 7 18 Channel configuration...
Page 157: ...156 7 Operating Control and Displays Fig 7 27 System CRCs menu...
Page 162: ...161 7 Operating Control and Displays Fig 7 32 IP setting menu...
Page 166: ...165 7 Operating Control and Displays Fig 7 35 Installation...
Page 167: ...166 7 Operating Control and Displays Fig 7 36 Installation...
Page 176: ...175 7 Operating Control and Displays Fig 7 49 Loading a protected dataset into the device...
Page 202: ...201 7 Operating Control and Displays Replacing a Module Fig 7 81 Module replacement menu...
Page 276: ...275 10 Maintenance 3 Restart CMS to complete the update...
Page 282: ...281 12 Appendix 12 5 EU Declaration of Conformity...
Page 283: ...282 12 Appendix...