Faults
No.
Description
D1
D2
Extra
257
Curve set change has failed
A curve set change was not completed until the time-
out expired.
– Reset fault
– If the fault still exists:
Send fault number and diagnostic code to the
technical support.
– Replace the device
0
0
R = 0
Reset
258
Internal fault
– Reset fault
– If the fault still exists:
Send fault number and diagnostic code to the
technical support.
– Replace the device
R = 0
Power ON Reset
259
Internal fault.
– Reset fault
– If the fault still exists:
Send fault number and diagnostic code to the
technical support.
– Replace the device
0
Fuel train
R = 0
Power ON Reset
260 - 278 Internal fault
0
0
– Reset fault
– If the fault still exists:
Send fault number and diagnostic code to the
technical support.
– Replace the device
281
Invalid curve data
Channel number
R = 0
Reset
285
Internal fault
– Reset fault
– If the fault still exists:
Send fault number and diagnostic code to the
technical support.
– Replace the device
286
Ignition position was left in IGNITION mode.
When using continuous output:
– Check the position-and speed of the channel which
is indicated in D1.
– If position and speed of the channel is OK:
Check EMC influences by ignition transformer. .
– If the speed and position are incorrect:
Check the settings of the frequency inverter
(analogue output)
– Check the smoothness of the control dampers
Fuel train
Internal
information
R = 1, 1, 1, 1
Reset
287
Band failure: Setpoint is not in the expected range.
The system detects a band failure. The setpoint
value has been exceeded.
Channel number
(starting at 0)
Setpoint feedback
R = 0, 0, 0, 0
Reset
Summary of Contents for CMS
Page 2: ......
Page 131: ...130 7 Operating Control and Displays 7 1 5 5 Deleting Curves Delete firing rate curve...
Page 148: ...147 7 Operating Control and Displays Channel configuration AL1 Fig 7 18 Channel configuration...
Page 157: ...156 7 Operating Control and Displays Fig 7 27 System CRCs menu...
Page 162: ...161 7 Operating Control and Displays Fig 7 32 IP setting menu...
Page 166: ...165 7 Operating Control and Displays Fig 7 35 Installation...
Page 167: ...166 7 Operating Control and Displays Fig 7 36 Installation...
Page 176: ...175 7 Operating Control and Displays Fig 7 49 Loading a protected dataset into the device...
Page 202: ...201 7 Operating Control and Displays Replacing a Module Fig 7 81 Module replacement menu...
Page 276: ...275 10 Maintenance 3 Restart CMS to complete the update...
Page 282: ...281 12 Appendix 12 5 EU Declaration of Conformity...
Page 283: ...282 12 Appendix...