253
9
Faults
No.
Description
D1
D2
Extra
101
Internal fault
– Reset fault
– If the fault still exists:
Send fault number and diagnostic code to the
technical support.
– Replace the device
102
Internal fault
– Reset fault
– If the fault still exists:
Send fault number and diagnostic code to the
technical support.
– Replace the device
103
Internal fault
– Reset fault
– If the fault still exists:
Send fault number and diagnostic code to the
technical support.
– Replace the device
104
Main relay failure
Phase or Neutral is missing at the power supply of
the digital output
Current relay
number
0
R = 0
Power ON Reset
105 - 114 Internal fault
0
0
– Reset fault
– If the fault still exists:
Send fault number and diagnostic code to the
technical support.
– Replace the device
115
Invalid configuration of the analogue input
Additional info 2:
0 = Configuration of the analogue input for current
measurement is not possible. The voltage at the cur-
rent input is currently too high, which leads to the
destruction of components.
1 = SafetyRAM contains an invalid configuration and
returns an invalid value if the configuration is redun-
dant.
Input number
0 = no current
measurement
1 = configuration
of SafetyRAM is
not plausible
R = 0
Reset
116
Analogue input: The reference voltage exceeds its
tolerance
The reference voltage of a safe analogue input
exceeds its tolerance.
Input number
Reference voltage
R = 0
Reset
117
Analogue input: Input current is too high
The voltage at the analogue input is at such a high
level after a self-test that the configuration as a cur-
rent input (activate shunt) leads to the destruction of
components.
Input number
Input current
R = 0
Reset
118
Different measured values at the analogue input
between main processor and watchdog processor.
– Reset fault
– If the fault still exists:
Send fault number and diagnostic code to the
technical support.
– Replace the device
Input number
Own signal
R = 0
Reset
Summary of Contents for CMS
Page 2: ......
Page 131: ...130 7 Operating Control and Displays 7 1 5 5 Deleting Curves Delete firing rate curve...
Page 148: ...147 7 Operating Control and Displays Channel configuration AL1 Fig 7 18 Channel configuration...
Page 157: ...156 7 Operating Control and Displays Fig 7 27 System CRCs menu...
Page 162: ...161 7 Operating Control and Displays Fig 7 32 IP setting menu...
Page 166: ...165 7 Operating Control and Displays Fig 7 35 Installation...
Page 167: ...166 7 Operating Control and Displays Fig 7 36 Installation...
Page 176: ...175 7 Operating Control and Displays Fig 7 49 Loading a protected dataset into the device...
Page 202: ...201 7 Operating Control and Displays Replacing a Module Fig 7 81 Module replacement menu...
Page 276: ...275 10 Maintenance 3 Restart CMS to complete the update...
Page 282: ...281 12 Appendix 12 5 EU Declaration of Conformity...
Page 283: ...282 12 Appendix...