220
8
CO/O
2
Control
Factory setting:
WARNING!
An incorrect setting can result in explosion.
This can result in severe injuries or death.
Note the adjustment instructions of the burner manufacturer with regard to the combus-
tion-related limit values.
Fig. 8-10 Correction with a spread factor of 20
Spread factor (P725 seq.)
Increase
Mode
Input
Neutral value
Correctional range*
20
2.0
+50 ... -50
0 % ... 100 %
50 %
P 705 ff.
Spread factor
10 Corresponds to 1.0 (i.e. no weighting)
Spread factor
>10 Correction effect increases as the burner efficiency increases
Spread factor
<10 Correction effect decreases as the burner efficiency decreases
Summary of Contents for CMS
Page 2: ......
Page 131: ...130 7 Operating Control and Displays 7 1 5 5 Deleting Curves Delete firing rate curve...
Page 148: ...147 7 Operating Control and Displays Channel configuration AL1 Fig 7 18 Channel configuration...
Page 157: ...156 7 Operating Control and Displays Fig 7 27 System CRCs menu...
Page 162: ...161 7 Operating Control and Displays Fig 7 32 IP setting menu...
Page 166: ...165 7 Operating Control and Displays Fig 7 35 Installation...
Page 167: ...166 7 Operating Control and Displays Fig 7 36 Installation...
Page 176: ...175 7 Operating Control and Displays Fig 7 49 Loading a protected dataset into the device...
Page 202: ...201 7 Operating Control and Displays Replacing a Module Fig 7 81 Module replacement menu...
Page 276: ...275 10 Maintenance 3 Restart CMS to complete the update...
Page 282: ...281 12 Appendix 12 5 EU Declaration of Conformity...
Page 283: ...282 12 Appendix...