57
4
CMS Components
NOTICE
The limits of the technical data must be strictly adhered to.
Part number
SDO Safe Digital Output component
Type 668R0500-XX
*
*
XX = depends on configuration
Function
Supply voltage
Module
Outputs
24 VDC (by connecting plugs from MCC)
230
V/120 V +10/-15
%,
47-63
Hz, 24 VDC ± 20 %
Backup fuse max. for outputs
8 A quick-acting
Current draw
Min: 40 mA
Max: 170 mA
Power consumption
5 W
Digital outputs
I
max
= 2 A per output
cos
φ
≥
0.2
Max. total current over all outputs: 8 A
Housing
Dimensions (H × W × D) [mm]
120 × 45.3 × 121
Weight [kg]
0,335
Flammability
UL94 V-0
Environmental conditions
Operation
Climatic conditions
Class 3K5 according to DIN EN 60721-3-3, 5-95%
Mechanical conditions
Class 3M5 according to DIN EN 60721-3-3
Temperature range
−
30 … +70°C (non-condensing)
Transportation
Climatic conditions
Class 2K4 according to DIN EN 60721-3-2,
95%
Mechanical conditions
Class 2M2 according to DIN EN 60721-3-2
Temperature range
−
40 … +80°C (non-condensing)
Storage
Climatic conditions
Class 1K3 according to DIN EN 60721-3-1, 5-95%
Mechanical conditions
Class 1M2 according to DIN EN 60721-3-1
Temperature range
−
40 … +80°C (non-condensing)
Electrical safety
IP rating according to DIN EN 60529
IP20 (as long as all terminals are mounted)
Summary of Contents for CMS
Page 2: ......
Page 131: ...130 7 Operating Control and Displays 7 1 5 5 Deleting Curves Delete firing rate curve...
Page 148: ...147 7 Operating Control and Displays Channel configuration AL1 Fig 7 18 Channel configuration...
Page 157: ...156 7 Operating Control and Displays Fig 7 27 System CRCs menu...
Page 162: ...161 7 Operating Control and Displays Fig 7 32 IP setting menu...
Page 166: ...165 7 Operating Control and Displays Fig 7 35 Installation...
Page 167: ...166 7 Operating Control and Displays Fig 7 36 Installation...
Page 176: ...175 7 Operating Control and Displays Fig 7 49 Loading a protected dataset into the device...
Page 202: ...201 7 Operating Control and Displays Replacing a Module Fig 7 81 Module replacement menu...
Page 276: ...275 10 Maintenance 3 Restart CMS to complete the update...
Page 282: ...281 12 Appendix 12 5 EU Declaration of Conformity...
Page 283: ...282 12 Appendix...