250
8
CO/O
2
Control
0006
O
2
fault
ot
od
O
2
measured value is outside the upper monitoring band.
The first upper monitoring band was exceeded for too long.
– Check the following and adjust if necessary:
– Correction range
– Electronic ratio control
– Setpoint curve
No.
O
2
faults –
information
Fault description
0008
O
2
fault
od
ot
O
2
measured value is outside the 1
st
lower monitoring band.
The first monitoring band was undershot for too long.
– Check the following and adjust if necessary:
– Correction range
– Electronic ratio control
– Setpoint curve
0009
O
2
fault
Half air shortage reached.
O
2
value is too small
– Expanded control strategy: Air supply is increased.
The automatic, expanded control strategy increases the air
supply.
0011
O
2
fault
Invalid O
2
measured value on LSB.
Lambda Transmitter is in cold start, adjustment mode or cali-
bration mode (do not measure).
– Wait until cold start has finished or leave adjustment mode
or calibration mode.
– Is LSB connected to Lambda Transmitter?
– Is Lambda Transmitter switched ON?
– Is LSB in fault condition (ERR LED is ON on LCM100)?
0012
O
2
setpoint curve is incorrect.
O
2
setpoint curve is empty or contains less than 3 points.
– Check and correct setpoint curve.
0013
O
2
fault
ot
Air deficiency: O
2
trim has been deactivated.
O2 actual value is permanently too small.
Due to insufficient air the control was deactivated.
A Replacement value for insufficient air is indicated as the cor-
rection.
0018
O
2
fault
od
Internal fault: O
2
setpoint curve is incorrect.
– Reset fault
– If the fault still exists:
Send error number and diagnostic code to the technical
support.
– Replace the device
0020
O
2
fault
Internal fault: O
2
trim fault
– Reset fault
– If the fault still exists:
Send error number and diagnostic code to the technical
support.
– Replace the device
No.
CO faults -
information
Fault description
Summary of Contents for CMS
Page 2: ......
Page 131: ...130 7 Operating Control and Displays 7 1 5 5 Deleting Curves Delete firing rate curve...
Page 148: ...147 7 Operating Control and Displays Channel configuration AL1 Fig 7 18 Channel configuration...
Page 157: ...156 7 Operating Control and Displays Fig 7 27 System CRCs menu...
Page 162: ...161 7 Operating Control and Displays Fig 7 32 IP setting menu...
Page 166: ...165 7 Operating Control and Displays Fig 7 35 Installation...
Page 167: ...166 7 Operating Control and Displays Fig 7 36 Installation...
Page 176: ...175 7 Operating Control and Displays Fig 7 49 Loading a protected dataset into the device...
Page 202: ...201 7 Operating Control and Displays Replacing a Module Fig 7 81 Module replacement menu...
Page 276: ...275 10 Maintenance 3 Restart CMS to complete the update...
Page 282: ...281 12 Appendix 12 5 EU Declaration of Conformity...
Page 283: ...282 12 Appendix...