213
8
CO/O
2
Control
8.7.2
Display in the Case of Active CO/O2 Control
8.7.2.1 Display with Active CO Control
The CO display replaces the O
2
display as soon as CO control is active.
NOTICE
re Items 2 and 4:
If this display value reaches -32 in case of air reduction (display of Item 2 = – and Item 4 = 32)
and +52 or +54 in case of air increase (display of Item 2 = + and Item 4 = 52 or 54), the CO
control has detected the CO edge and the optimisation point is saved.
8.7.2.2 Display for Active O
2
Trim
8.7.2.3 Status Display in Case of O2 Trim
Fig. 8-4 Display for active CO control
1
CO actual value [ppm]
2
– = air is reduced
+ = air is increased
3
C = increasing firing rate
c = falling firing rate
4
Number of optimisation steps
5
O
2
actual value – in this case 1.1 vol. %
O
2
Fig. 8-5 Display for active O
2
trim
1
O
2
actual value
2
O
2
setpoint value
3
Status display
op
O
2
trim ready (at burner startup) or O
2
trim switched off temporarily depending on fir-
or
O
2
trim active (see Chapter
ot
O
2
trim temporarily deactivated (insufficient air, O
2
value under the monitoring bands,
etc.)
od
O
2
trim permanently deactivated (malfunction), e.g., test routines at burner startup
not passed, dynamics test negative, O
2
trim temporarily deactivated for longer than
an hour, etc. (see chapter
Summary of Contents for CMS
Page 2: ......
Page 131: ...130 7 Operating Control and Displays 7 1 5 5 Deleting Curves Delete firing rate curve...
Page 148: ...147 7 Operating Control and Displays Channel configuration AL1 Fig 7 18 Channel configuration...
Page 157: ...156 7 Operating Control and Displays Fig 7 27 System CRCs menu...
Page 162: ...161 7 Operating Control and Displays Fig 7 32 IP setting menu...
Page 166: ...165 7 Operating Control and Displays Fig 7 35 Installation...
Page 167: ...166 7 Operating Control and Displays Fig 7 36 Installation...
Page 176: ...175 7 Operating Control and Displays Fig 7 49 Loading a protected dataset into the device...
Page 202: ...201 7 Operating Control and Displays Replacing a Module Fig 7 81 Module replacement menu...
Page 276: ...275 10 Maintenance 3 Restart CMS to complete the update...
Page 282: ...281 12 Appendix 12 5 EU Declaration of Conformity...