233
8
CO/O
2
Control
Fig. 8-24 Analogue measurement values window
No change or change is too small
increase P term in P 110.
NOTICE
The new correction is determined as a function of the actual/setpoint deviation of the O2 value,
the P factor and the spread factor. This is then sent to the CMS. The procedure is repeated
after the dead time has elapsed. If the internal firing rate changes during this time, the O
2
trim
switches to the FEED FORWARD CONTROL mode. The correction value follows the stored
optimisation curve.
Activating CO Control
Fig. 8-25 Open the CO controller menu
NOTICE
To open the menu at least access level 1 is required. (CMS, V1.0.3).
Summary of Contents for CMS
Page 2: ......
Page 131: ...130 7 Operating Control and Displays 7 1 5 5 Deleting Curves Delete firing rate curve...
Page 148: ...147 7 Operating Control and Displays Channel configuration AL1 Fig 7 18 Channel configuration...
Page 157: ...156 7 Operating Control and Displays Fig 7 27 System CRCs menu...
Page 162: ...161 7 Operating Control and Displays Fig 7 32 IP setting menu...
Page 166: ...165 7 Operating Control and Displays Fig 7 35 Installation...
Page 167: ...166 7 Operating Control and Displays Fig 7 36 Installation...
Page 176: ...175 7 Operating Control and Displays Fig 7 49 Loading a protected dataset into the device...
Page 202: ...201 7 Operating Control and Displays Replacing a Module Fig 7 81 Module replacement menu...
Page 276: ...275 10 Maintenance 3 Restart CMS to complete the update...
Page 282: ...281 12 Appendix 12 5 EU Declaration of Conformity...
Page 283: ...282 12 Appendix...