261
9
Faults
No.
Description
D1
D2
Extra
245
Fuel valves are OPEN in spite of malfunction.
The fuel valves are open although a fault is pending.
– Reset fault
– If the fault still exists:
Send fault number and diagnostic code to the
technical support.
– Replace the device
Internal
information
0
R = 0
Power ON Reset
246
No fault shut-down of the FAT although a fault is
pending.
– Reset fault
– If the fault still exists:
Send fault number and diagnostic code to the
technical support.
– Replace the device
Internal
information
0
R = 0
Power ON Reset
247
Pilot air pressure is missing.
No air pressure for the pilot burner.
– Check air pressure switch
– Check fan
Internal
Information
0
R = 0, 0, 0, 0
Reset
248
Valve leakage test: Gas pressure is still present.
Main valve 1 is leaking
– Check gas pressure switch for function
– Is main valve 2 opened during the test?
No: check the valve, replace if necessary
check
wiring
– Check output pressure at the main valves during
the venting of the test line.
If the outlet pressure is higher than the adjusted gas
pressure at the pressure switch, take the following
measures:
– Re-adjust the pressure switch and recalculate the
detected leakage rate (observe local standards
and guidelines).
– Reduce the aperture of the air damper for venting
– If the fault still exist: change main valve 1
Internal
Information
Fuel train
R = 0, 0, 0, 0
Reset
249
Valve leakage check: Gas pressure is still present.
Main valve 2 is leaking
– Check gas pressure switch for function
– Is main valve 1 opened during the test?
No: check the valve, replace if necessary
check
wiring
– Check output pressure at the main valves
during the venting of the test line.
If the outlet pressure is higher than the
adjusted gas pressure at the pressure switch,
take the following measures:
– Re-adjust the pressure switch and recalculate
the detected leakage rate (observe local
standards and guidelines).
– Reduce the aperture of the air damper for
venting
– If the fault still exist: change main valve 2
Internal
information
Fuel train
R = 0, 0, 0, 0
Reset
Summary of Contents for CMS
Page 2: ......
Page 131: ...130 7 Operating Control and Displays 7 1 5 5 Deleting Curves Delete firing rate curve...
Page 148: ...147 7 Operating Control and Displays Channel configuration AL1 Fig 7 18 Channel configuration...
Page 157: ...156 7 Operating Control and Displays Fig 7 27 System CRCs menu...
Page 162: ...161 7 Operating Control and Displays Fig 7 32 IP setting menu...
Page 166: ...165 7 Operating Control and Displays Fig 7 35 Installation...
Page 167: ...166 7 Operating Control and Displays Fig 7 36 Installation...
Page 176: ...175 7 Operating Control and Displays Fig 7 49 Loading a protected dataset into the device...
Page 202: ...201 7 Operating Control and Displays Replacing a Module Fig 7 81 Module replacement menu...
Page 276: ...275 10 Maintenance 3 Restart CMS to complete the update...
Page 282: ...281 12 Appendix 12 5 EU Declaration of Conformity...
Page 283: ...282 12 Appendix...