246
8
CO/O
2
Control
8.11.3
CO Controller Faults
CO fault example:
When the following monitoring routines are activated, CO control is deactivated. Depending
on the settings made, CO optimisation is completely deactivated (factory setting) or switched
to O
2
trim online.
Fig. 8-39 Display of a CO monitoring fault
The plausibility check of the sensor voltage
of the CO
e
measuring cell with O
2
trim has
been activated.
No.
Fault/
information
Comment
0040
CO fault
ot
There is no CO edge information available on the LAMTEC SYSTEM
BUS.
Lambda Transmitter is incorrectly configured or not connected to LSB.
LSB connection is twisted.
(see chapter
8.8 Electrical Connection - Connection via LSB
Lambda Transmitter is not in measuring mode (malfunction/cold start).
Lambda Transmitter is in adjustment mode.
The correction range is set too small. As a result, the control
cannot approach the CO edge.
– Check correction range (P703) and adjust if necessary.
The electronic ratio curve is set in such a way that the CO edge cannot
be reached.
– Check curve setting and adjust l if necessary.
With CO, the LT does not achieve the necessary probe dynamics for
triggering the CO edge.
– Check the trigger threshold for the edge signal in the LT and
adjust it if necessary.
0041
CO fault
ot
CO probe voltage is outside the monitoring window (U
CO/H2
).
Incorrect polarity of probe connection (signal).
The probe is defective.
Permissible probe voltage range in Lambda Transmitter is too small.
Range: +10 ... + 500 mV
0042
CO fault
ot
CO probe offset is outside the monitoring window.
During the offset calibration process 21 % O2 (air) were not present at
the measuring point.
– Repeat offset calibration
The probe heats up.
– Check internal probe resistance Ri in LT
– Check wiring and correct if necessary
The probe is defective.
Fault in the wiring (incorrect polarity)
Range: -25 ... +10 mV/20 s
Summary of Contents for CMS
Page 2: ......
Page 131: ...130 7 Operating Control and Displays 7 1 5 5 Deleting Curves Delete firing rate curve...
Page 148: ...147 7 Operating Control and Displays Channel configuration AL1 Fig 7 18 Channel configuration...
Page 157: ...156 7 Operating Control and Displays Fig 7 27 System CRCs menu...
Page 162: ...161 7 Operating Control and Displays Fig 7 32 IP setting menu...
Page 166: ...165 7 Operating Control and Displays Fig 7 35 Installation...
Page 167: ...166 7 Operating Control and Displays Fig 7 36 Installation...
Page 176: ...175 7 Operating Control and Displays Fig 7 49 Loading a protected dataset into the device...
Page 202: ...201 7 Operating Control and Displays Replacing a Module Fig 7 81 Module replacement menu...
Page 276: ...275 10 Maintenance 3 Restart CMS to complete the update...
Page 282: ...281 12 Appendix 12 5 EU Declaration of Conformity...
Page 283: ...282 12 Appendix...