248
8
CO/O
2
Control
0052
CO fault
ot
The CO edge signal is not plausible.
The CO edge signal was present constantly for more than 60 s.
The controller cannot control out of the CO.
– Check/adjust the triggering threshold for the CO edge on the
LT.
– Check/adjust correction range (P703).
– Check/adjust electronic ratio curves.
– Check/replace probe for correct function.
– Check/replace LT
0053
CO fault
ot
The CO edge signal is not plausible.
Permanent CO controller switch-off.
CO edge signal persisted for more than 300 s.
– Reset fault by a manual acknowledgement of the fault
or with a burner restart
– Check/adjust correction range (P703).
– Check/adjust electronic ratio curves.
– Check/replace probe for correct function.
– Check/replace LT
0054
CO fault
ot
The CO edge has been exceeded for too long after ignition.
The CO edge has been exceeded permanently for more than 120 s. The
controller cannot control out of the CO.
– Check/adjust the triggering threshold for the CO edge on the
LT.
– Check/adjust correction range (P703).
– Check/adjust electronic ratio curves (ignition point).
– Check/replace probe for correct function.
– Check/replace LT
0055
CO fault
od
The CO edge has been exceeded for too long after ignition.
The CO edge has been exceeded permanently for more than 240 s.
The controller cannot control out of the CO.
The CO detection can be switched off after ignition by P234
(P 234
0)
– Check/adjust the triggering threshold for the CO edge on the
LT.
– Check/adjust correction range (P703).
– Check/adjust electronic ratio curves (ignition point).
– Check/replace probe for correct function.
– Check/replace LT
No.
Fault/
information
Comment
Summary of Contents for CMS
Page 2: ......
Page 131: ...130 7 Operating Control and Displays 7 1 5 5 Deleting Curves Delete firing rate curve...
Page 148: ...147 7 Operating Control and Displays Channel configuration AL1 Fig 7 18 Channel configuration...
Page 157: ...156 7 Operating Control and Displays Fig 7 27 System CRCs menu...
Page 162: ...161 7 Operating Control and Displays Fig 7 32 IP setting menu...
Page 166: ...165 7 Operating Control and Displays Fig 7 35 Installation...
Page 167: ...166 7 Operating Control and Displays Fig 7 36 Installation...
Page 176: ...175 7 Operating Control and Displays Fig 7 49 Loading a protected dataset into the device...
Page 202: ...201 7 Operating Control and Displays Replacing a Module Fig 7 81 Module replacement menu...
Page 276: ...275 10 Maintenance 3 Restart CMS to complete the update...
Page 282: ...281 12 Appendix 12 5 EU Declaration of Conformity...
Page 283: ...282 12 Appendix...