115
6
Commissioning
Factory setting of the shutdown limit for O
2
monitoring with active CO control = 0.4 vol.%.
Checking the O
2
effect
1. Run to the shut-off limits
2. Check the correction influence
NOTICE
If the factory-set switch-off limit of 0.4 vol.% O
2
is too low for the application, it can be raised
using the CMS Remote Software (AL4). If necessary, contact LAMTEC Support:
[email protected]
+49 (0) 6227 6052-33
’How to’ see chapter
Summary of Contents for CMS
Page 2: ......
Page 131: ...130 7 Operating Control and Displays 7 1 5 5 Deleting Curves Delete firing rate curve...
Page 148: ...147 7 Operating Control and Displays Channel configuration AL1 Fig 7 18 Channel configuration...
Page 157: ...156 7 Operating Control and Displays Fig 7 27 System CRCs menu...
Page 162: ...161 7 Operating Control and Displays Fig 7 32 IP setting menu...
Page 166: ...165 7 Operating Control and Displays Fig 7 35 Installation...
Page 167: ...166 7 Operating Control and Displays Fig 7 36 Installation...
Page 176: ...175 7 Operating Control and Displays Fig 7 49 Loading a protected dataset into the device...
Page 202: ...201 7 Operating Control and Displays Replacing a Module Fig 7 81 Module replacement menu...
Page 276: ...275 10 Maintenance 3 Restart CMS to complete the update...
Page 282: ...281 12 Appendix 12 5 EU Declaration of Conformity...
Page 283: ...282 12 Appendix...