The sequence that the lights turn on are
as follows:
1.
Control Power (Amber)
2.
Overload Relay (Amber)
3.
E-Stop (Amber)
4.
Stop (Amber)
5.
Start (Amber)
6.
24VDC (Green)
Troubleshooting Electrical Problems
6-26
KVAL Operation/Service Manual
If one or more lights are OFF, follow the process below to isolate the cause.
NOTE
: Be sure to proceed down the table, starting with the CONTROL POWER light.
STEP 1:Control Power (Amber). If light is OFF go to item
A
on page
6-27.
STEP 2:Overload Relay (Amber) If light is OFF go to item
B
on page
6-28.
STEP 3:E-Stop (Amber) If light is OFF go to item
C
on page
6-28.
STEP 4: Stop (Amber) If light is OFF go to item
D
on page
6-28.
STEP 5: Start (Amber) If light is OFF go to item
E
on page
6-29.
STEP 6: 24VDC (Green light is OFF go to item
F
on page
6-29.