Characteristic
Value
Frequency [MHz]
13.56
Emitted maximum transmitting power at 10 m dis‐
tance [dB(µA/m)]
11
Tab. 13 RFID
The RFID read/write device transmits at a frequency of 13.56 MHz and is permitted for use in
EU member states.
3.1.3 In- and outputs with MCSIO
Integrated in- and outputs with MCSIO type controller
Input/Output
Number
Digital input (DI), 24 VDC
8
Digital output transistor (DOT), 24 VDC, 0.5 A
2
Analogue input current (AII), 0–20 mA
2
Analogue input resistor (AIR), PT100
2
Digital output relay (DOR), 250 VAC, 4 A
5
Tab. 14 Number of internal inputs and outputs
3.1.3.1 Maximum cable lengths
Input/Output
Cable length [m]
Analogue input current (AII),
Analogue input resistor (AIR)
Analogue output current (AOI)
< 30
Digital input (DI),
Digital output relay (DOR)
< 100
Digital output transistor (DOT)
< 30
Tab. 15 Cable lengths
3.1.4 Input/output modules
IOM modules only in combination with the MCS controller type
There are three different types of input/output modules with different numbers of inputs and out‐
puts.
The number of input/output modules actually available depends on the machine type and the avail‐
able options.
Refer to the machine's wiring diagram for the input/output modules installed in your equipment.
Every input/output module is equipped with:
■ Internal temperature monitoring
3
Technical Specifications
3.1
Controller SIGMA CONTROL 2
No.: 9_9450 12 E
User Manual Controller
SIGMA CONTROL 2 SCREW FLUID ≥5.0.X
13