1. Open the 5.7.4
<Configuration – I/O periphery – Switch> menu.
A menu containing a list of available measured values is displayed.
6 . 1 b a r
0 8 : 1 5 A M
8 0 ° C
Header
5.7.4 Switch
Menu
▶1 System pressure pNloc
Active line
▶2 Internal pressure pi
▶3 ADT
▶4 Inlet temperature
▶5 PD temperature
▶6 n Compressor motor
2. Use «Up» or «Down» to select the measured value.
3. Press «Enter».
The menu for the selected measured value (in the example
System pressure pNloc) is dis‐
played.
6 . 1 b a r
0 8 : 1 5 A M
8 0 ° C
Header
5.7.4.1 System pressure pNloc
Menu
active:
☐
active line with check box
·········
SP:
2.25bar ¦ SD:
0.0bar
Switching point (SP) and switching differential (SD)
td:
0s ¦Logic
+
Delay (td) and logic
DOR1.01
☐
Output DOR
Operation
☐
Type of message
8.12.4.1 Setting the switching point and switching differential
1. Use «Up» or «Down» to select the
SP line.
6 . 1 b a r
0 8 : 1 5 A M
8 0 ° C
Header
5.7.4.1 System pressure pNloc
Menu
active:
☐
·········
SP:
0.50bar ¦ SD:
−0.6bar
Switching point (SP) and switching differential (SD)
td:
0s ¦Logic
+
Delay (td) and logic
DOR1.01
☐
Output DOR
Operation
☐
Type of message
2. Press «Enter».
The display for the current threshold of the switching point flashes.
3. Use the «Up» or «Down» keys to set the
SP threshold.
4. Press «Enter».
The setting is applied.
5. If necessary, adjust the value for the
SD switching differential in the same way.
Result The threshold for the
SP switching point and the SD switching differential are set.
8
Initial Start-up
8.12 Setting input and output signals
166
User Manual Controller
SIGMA CONTROL 2 SCREW FLUID ≥5.0.X