8.15 Linking to an external pressure transducer
If the air system is operated with an air receiver, the pressure in the receiver can be regulated by
an external pressure transducer.
Transmitting a pressure transducer value
Assignment to an input
The external pressure transducer is connected to
SIGMA CONTROL 2.
AII assign
Pressure transducer characteristics:
■ 4–20 mA
■ 0–16.0 bar
Tab. 80 Transmitting a pressure transducer value
The controller processes the options in the following sequence:
■ Pressure according to the assigned external transducer
■ The local system pressure transducer (pNloc) remains active.
Overview
Example: The external pressure transducer is connected to SIGMA CONTROL 2.
■ Open the
<Configuration – Pressure control> menu.
■ Assigning an input
8.15.1 Pressure control menu
Precondition Access level 2 is activated.
1. Open the 5.2.4
< Configuration – Pressure control – Network actual pressure> menu.
The
Network actual pressure menu is displayed
6 . 1 b a r
0 8 : 1 5 A M
8 0 ° C
Header
5.2.4 Network actual pressure
Menu
pNloc
6.1bar
Active line (local pressure transducer)
AII1.01
☐
0.0bar
For sensor error:
Alarm
8.15.2 Assigning an input to an external pressure transducer
1. Press «Enter».
The
pNloc indication flashes.
8
Initial Start-up
8.15 Linking to an external pressure transducer
No.: 9_9450 12 E
User Manual Controller
SIGMA CONTROL 2 SCREW FLUID ≥5.0.X
173