4. Use «Up» or «Down» to set the
pA value.
5. Press «Enter».
The setting is applied.
6. If necessary, adjust the value for
SD in the same manner.
7. If necessary, adjust the value for
pB/SD in the same manner.
8. Press «Escape» repeatedly to leave this menu.
Set clock program
➤ Set the clock program as described in chapter 8.10.2.
8.11.9 Examples of time settings for equal overall load
Requirement:
Two machines with comparable flow rate are to be equally utilized. Versions A, B and C describe
the different possibilities of achieving this requirement.
A detailed description for creating a timing program or setting the timer can be found in Chap‐
Variant A: Daily switch between network nominal pressure pA and network nominal pressure pB
after 24 hours
The machines start with a network nominal pressure
pB at 0:00 hours. A timer triggers the switch
between network nominal pressure
pA and network nominal pressure pB (local operating mode:
pA/pB Cycle local mode).
Precondition The network nominal pressure
pA/pB is configured the same for both machines.
➤ Establish a cycle with the following switching points:
■ Cycle time
pA: 24 h
■ Cycle time
pB: 24 h
■ Start
pB: 00:00AM
Variant B: Equal duty cycle during the day
A timer triggers the switch between network nominal pressure
pA and network nominal pressure
pB (local operating mode pA/pB Clock.
Precondition The network nominal pressure
pA/pB is configured the same for both machines.
➤ The clock program is set up using the following switching points:
No.:
Weekday
Time
Network nominal pressure
01
Mon-Sun
00:00AM
pA On
02
Mon-Sun
06:30AM
pB On
03
Mon-Sun
12:00PM
pA On
04
Mon-Sun
05:00PM
pB On
Tab. 74 Example for a clock program for equal duty cycling during the day
8
Initial Start-up
8.11 Setting the machine for master control operation
152
User Manual Controller
SIGMA CONTROL 2 SCREW FLUID ≥5.0.X
No.: 9_9450 12 E