1. Open the 5.3.2
<Configuration – Control mode – DUAL> menu.
6 . 1 b a r
0 8 : 1 5 A M
8 0 ° C
Header
5.3.2 DUAL
Menu
Idle period
Target
240s ¦ Actual
0s
active line
2. Use «Up» or «Down» to select the
Target line.
6 . 1 b a r
0 8 : 1 5 A M
8 0 ° C
Header
5.3.2 DUAL
Menu
Idle period
Target
300s ¦ Actual
0s
increased idle time (e.g. 300 s)
3. Press «Enter».
The seconds display flashes.
4. Use «Up» or «Down» to set the seconds.
5. Press «Enter».
The setting is applied.
6. Press «Escape» repeatedly to leave this menu.
8.7.3 Setting the QUADRO control mode
When the minimum running period has elapsed, the machine switches from IDLE to READY. The
expired duration of the unloaded period controls whether the machine switches from IDLE to
READY only after expiry of the set unloaded period or after expiry of the venting period.
Precondition Access level 2 is activated.
The QUADRO control mode is set.
1. Open the 5.3.3
<Configuration – Control mode – QUADRO> menu.
6 . 1 b a r
0 8 : 1 5 A M
8 0 ° C
Header
5.3.3 QUADRO
Menu
Min. run period
Target
240s ¦ Actual
0s
Set value for minimum run-time
·········
Unloaded period
Target
240s ¦ Actual
0s
Set value for unloaded period
8
Initial Start-up
8.7
Control modes
No.: 9_9450 12 E
User Manual Controller
SIGMA CONTROL 2 SCREW FLUID ≥5.0.X
107