8.12.3.4 Setting the switching point and switching differential
1. Use «Up» or «Down» to select the
SP line.
6 . 1 b a r
0 8 : 1 5 A M
8 0 ° C
Header
5.7.2.1.1 AnMod_p_1
Menu
AnMod_p_1 Title
0.0 bar
Message text
pNloc
☑
selected analogue measured value, activated
·········
SP:
8.0bar ¦ SD:
−0.5bar
Switching point (SP) and switching differential (SD)
td:
0s
Time delay (td)
·········
2. Press «Enter».
The display for the current value of the switching point flashes.
3. Use «Up» or «Down» to set the
SP value.
4. Press «Enter».
The setting is applied.
5. If necessary, adjust the value for SD in the same manner
Result The threshold value for the SP switching point and the SD switching differential are set.
8.12.3.5 Set the time delay
The delay can be set between 0 and 600 seconds. The delay is counted down from 600 in 1
second increments with the «DOWN» key and counted upwards from 0 (zero) in 1 second
increments with the «UP» key.
1. Use «Up» or «Down» to select the
td line.
2. Press «Enter».
The
td delay time flashes.
6 . 1 b a r
0 8 : 1 5 A M
8 0 ° C
Header
5.7.2.1.1 AnMod_p_1
Menu
AnMod_p_1 Title
0.0 bar
Message text
pNloc
☑
selected analogue measured value, activated
·········
SP:
8.0bar ¦ SD:
−0.5bar
Switching point (SP) and switching differential (SD)
td:
0s
Time delay (td)
·········
3. Use «Up» or «Down» to set the time delay in seconds.
4. Press «Enter».
Result The
td delay time has been set.
8.12.3.6 Setting the message type
1. Select the message type line with the «Up» and «Down» keys.